Plan Review Notes
Plan Review Notes For Permit 20040077
Permit Number 20040077
Review Stop G
Sequence Number 2
Notes
Date Text
2020-05-21 07:25:15 
 1ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT #20040077
 5/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING:
 A) INDICATE THE TOTAL DEVELOPED LENGTH OF THE GAS
 PIPING SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET.
 THIS INCLUDES THE EXISTING AND THE NEW PIPING-
 SECTIONS- G2413.4.1 & G2413.4.2 FBC RES. THE CURRENT
 ISOMETRIC DOES NOT SHOW THE PIPING RUN AND BRANCH LINES
 TO THE EXISTING APPLIANCES IN THE HOUSE. A THOROUGH
 REVIEW OF THE PIPE SIZING CANNOT BE ACCOMPLISHED
 WITHOUT A COMPLETE DRAWING AND THE TOTAL DEVELOPED
 LENGTH OF THE SYSTEM- SECTIONS G2412.4 G2412.8, G2413.1
 & G2413.3 FBC RES.
 B) SHOW THE SHUT OFF VALVE LOCATIONS AT THE NEW METER,
 AND AT THE NEW 2 PSI-11" WC REGULATOR- SECTION 2420.1
 FBC RES. NOTE: WHERE CONNECTED TO RIGID PIPING, A UNION
 SHALL BE INSTALLED WITH 1 FT OF EITHER SIDE OF AN MP
 REGULATOR- SECTION G2421.2 FBC RES
 C) INDICATE THE SENSUS REGULATOR MODEL NUMBERS AND
 ORIFICE SIZES ON THE DRAWING. PLEASE PROVIDE A COMPLETE
 SUBMITTAL FOR THE REGULATORS. THERE ARE NO TECHNICAL
 DATA SHEETS PROVIDED TO VERIFY ORIFICE SIZING BASED ON
 OUTLET PRESSURES AND BODY SIZES- SECTION G2421.1 FBC
 RES.
 D) THERE IS A 3/4" PIPE TEED OFF INTO SPACE POSSIBLY
 FOR A FUTURE APPLIANCE- PLEASE INDICATE THE TYPE OF
 PIPING AND CLARIFY IT'S PURPOSE- SECTION 107.2.1 WPB.
 E) IDENTIFY THE TYPE OF PIPING FROM THE METER TO THE
 NEW HOUSE REGULATOR, AND SHOW THE CUT LENGTH OF THE
 PIPE FROM THE 1" TEE TO THE NEW REGULATOR- SECTION
 G2413.4.1 & G2413.4.2
  
 2) SURVEY: THE GENERATOR SHALL BE LOCATED AT A MINIMUM
 OF 5' FROM THE ADJACENT EXTERIOR WALL, OR VERIFY THE
 WALL HAS A 1-HR. FIRE RESISTANCE RATING- SECTION 4.1.4
 (1) NFPA 54. A) INDICATE A MINIMUM 10' CLEARANCE FROM
 THE GENERATOR TO AIR INTAKES AND OPERABLE OPENINGS INTO
 THE BUILDING WILL BE MAINTAINED PER SECTION R303.5.1
 FBC RES.
  
 3) PLEASE ADJUST THE COST VALUE OF THE PROJECT TO
 INCLUDE INSTALLATION OF THE NEW GAS METER- SECTION
 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  