Plan Review Notes For Permit 20040036 |
Permit Number |
20040036 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-04-16 11:45:50 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PROJECT IS LOCATED IN AN SPECIAL FLOOD HAZARD | | AREA , "AE". THE NEW GENERATOR IS REQUIRED TO BE | | LOCATED AT OR ABOVE 9' NAVD88. FBC R322 AND CITY FLOOD | | ORDINANCE | | | | 2) SUBMIT ORIGINAL SIGNED AND SEALED WINDLOAD | | ENGINEERING FOR THE PROPOSED PREFABRICATED GENERATOR | | PAD. FBC R301.1 |
|