Plan Review Notes For Permit 20040033 |
Permit Number |
20040033 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-05-07 15:19:12 | PLAN | | REVIEW COMMENTS | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) I AM NOT ABLE TO VERIFY THE DIGITAL SIGNATURE ON THE | | GENERATOR PAD DOCUMENT THAT WAS SUBMITTED. IF THE | | DOCUMENT PRINTED OUT AND THEN UPLOADED THE DIGITAL | | SIGNATURE IS VOIDED. EACH SHEET OF THE DOCUMENT IS | | REQUIRED TO BE SIGNED AND SEALED, UNLESS A COVERSHEET | | LISTING ALL OF THE PAGES IS USED. FS 471 & FAC 61G-15 | | 2) THE ENGINEERED DOCUMENTS FOR THE GENERATOR PAD | | SPECIFIES A VULT WINDSPEED OF 165MPH AND THE WINDSPEED | | FOR THIS PROJECT IS 170MPH. CITY AMENDMENTS FBC 120.1 | | |
|