2020-05-19 08:38:07 | 1) THE PLANS SHOW AN EXISTING GAS METER AND EXISTING | | GAS SYSTEM AND APPLIANCES. CITY RECORDS DO NOT SHOW ANY | | PERMITS FOR THIS EXISTING SYSTEM. THE EXISTING SYSTEM | | MUST BE LEGALLY PERMITTED PER WPB AMEND. TO FBC SEC. | | 105.1. | | 2) THE SHUTOFF VALVE ON THE EXISTING GAS LINE SHALL BE | | LOCATED AHEAD OF THE REGULATOR PER FBC-FUEL GAS | | SEC.409.4. | | 3) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE | | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE | | REGULATOR. FBC-FUEL GAS SEC.410.2 (7). | | 4) THE BTU LOAD OF THE NEW GENERATOR IS SHOWN AS | | 281,000 BTU'S AND ALSO AS 327,000 BTU'S. CLARIFY. NOTE: | | THE SPECIFICATIONS CALL OUT 327,000 BTU'S. | | 5) SUBMIT MANUF. SPECS ON THE REGULATORS. REGULATORS | | INSTALLED ON THE EXTERIOR OF A STRUCTURE SHALL BE | | APPROVED FOR OUTDOOR USE. FBC-FUEL GAS 410.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|