Plan Review Notes
Plan Review Notes For Permit 20040033
Permit Number 20040033
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-19 08:38:071) THE PLANS SHOW AN EXISTING GAS METER AND EXISTING
 GAS SYSTEM AND APPLIANCES. CITY RECORDS DO NOT SHOW ANY
 PERMITS FOR THIS EXISTING SYSTEM. THE EXISTING SYSTEM
 MUST BE LEGALLY PERMITTED PER WPB AMEND. TO FBC SEC.
 105.1.
 2) THE SHUTOFF VALVE ON THE EXISTING GAS LINE SHALL BE
 LOCATED AHEAD OF THE REGULATOR PER FBC-FUEL GAS
 SEC.409.4.
 3) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE
 REGULATOR. FBC-FUEL GAS SEC.410.2 (7).
 4) THE BTU LOAD OF THE NEW GENERATOR IS SHOWN AS
 281,000 BTU'S AND ALSO AS 327,000 BTU'S. CLARIFY. NOTE:
 THE SPECIFICATIONS CALL OUT 327,000 BTU'S.
 5) SUBMIT MANUF. SPECS ON THE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF A STRUCTURE SHALL BE
 APPROVED FOR OUTDOOR USE. FBC-FUEL GAS 410.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  