2020-04-13 08:22:42PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW - GARAGE/APARTMENT
  
 RESULTS: PENDING STAND ALONE ELECTRICAL PERMIT PER EOR.
 THE FOLLOWING COMMENTS ARE FOR REFERENCE ONLY.
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SCOPE OF WORK INCLUDES THE ADDITION OF A NEW SINK AND
 COUNTERTOP, WASHER & DRYER AND RE-LOCATION OF BATHROOM
 VANITY ON 1ST FLOOR AND ADDITION OF NEW SINK AND
 COUNTERTOP ON 2ND FLOOR.
  
 1. ELECTRICAL PERMIT REQUIRED.
 PERMITS 105.1 REQUIRED.
  
 2. PROVIDE AN ELECTRICAL PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PROVIDE AN ELECTRICAL RISER DIAGRAHM.
 RISER:
  
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
  
 PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5;
 WPB FBC 107.2.1
  
  
 4. PROVIDE NEW PANEL SCHEDULE.
 PANEL SCHEDULE:
  
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 5. PROVIDE NEW LOAD CALCULATIONS.
 LOAD CALC.:
  
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2
  
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT EXISTING PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10 & FBC RE E3404.3
  
 PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC
 110.3, 110.9; FBC RE E3606.4
  
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24 & FBC RE E3606.4
  
 NAME AND SIGNATURE OF DESIGNER OF RECORD SEC 107.3.4.1
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  