Plan Review Notes
Plan Review Notes For Permit 20031435
Permit Number 20031435
Review Stop P
Sequence Number 1
Notes
Date Text
2020-04-02 13:13:39RESULTS ENTERED BY JOHN PEARSON FOR REVIEW BY JERRY
 SMITH:
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20031435 140 MONROE DR
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PLAN APPEARS TO BE A SCANNED COPY OF PAPER PLAN WITH
 ENGINEER?S STAMP. PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. THE DIGITAL SIGNATURE MUST INCLUDE
 THE STATEMENT "SIGNED AND SEALED" AS PER FAC
 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
 2. RE: HYDRAULIC CALCULATIONS; PER WPB FBC 107.2. 1 AND
 APSP-7-2013, INCLUDE THE HEAD LOSS FOR THE POOL HEATER
 AS WELL AS THE VALVES AND FITTINGS. ADDITIONALLY, ALL
 EQUIPMENT SUBMITTALS SHALL BE CLEAR, EASILY READ AND
 SHALL INCLUDE ALL PERTINENT TECHNICAL INFORMATION
 INCLUDING BUT NOT LIMITED TO HYDRAULIC FLOW AND HEAD
 LOSS.
 3. RE: PUMP PERFORMANCE CURVE CHART ON PLAN SHEET 3 OF
 4; TEXT IN DESCRIPTION BLOCKS AT END OF EACH CURVE IS
 BLURRED. PER WPB FBC 107.2.1, PROVIDE CLEAN CHART.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS REQUIREMENTS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
  