Plan Review Notes
Plan Review Notes For Permit 20031395
Permit Number 20031395
Review Stop G
Sequence Number 4
Notes
Date Text
2020-06-03 09:41:164TH REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20031395
 6/3/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE REQUIRED PLAN CORRECTIONS LISTED BELOW WERE
 DISCUSSED IN A TELEPHONE CALL WITH THE NEW ENGINEER OF
 RECORD- DANIEL RIVEROS PE. MR. RIVEROS WILL CORRECT THE
 PLANS ACCORDINGLY.
  
 1) SHEET G-02, GAS RISER: SHOW THE SIZE OF THE INCOMING
 GAS PIPE TO THE METER AND PROVIDE THE CORRECT SIZING
 TABLE FOR A 2 PSI SYSTEM- TABLE 402.4(5) FBC FG. PLEASE
 NOTE THAT TABLE 402.4(2) IS THE SIZING TABLE FOR LESS
 THAN 2 PSI WHICH WOULD BE THE PRESSURE DOWNSTREAM OF
 THE REGULATOR.
  
 2) G-02, GAS RISER: PROVIDE THE LENGTHS OF THE 1.2" AND
 3/4" BRANCH PIPES SUPPLYING THE RANGE AND THE WATER
 HEATER FROM THE 1" TEE. PLEASE SEE TABLE 402.4(2)- THE
 3/4" BRANCH PIPE TO THE WATER HEATER IS UNDERSIZED AND
 MUST BE INCREASED TO A 1" PIPE.
  
 3) G-02, GAS RISER: THE SPECS FOR THE NAVIEN GAS WATER
 HEATER INDICATE A MAXIMUM 10.5 "WC PRESSURE TO THE
 UNIT. PLEASE PLACE A NOTE BY THE REGULATOR AND SUBMIT
 SPECS- G2408.1 FBC RES.
  
 4) G-01: PLACE A NOTE TO INDICATE THE LENGTH OF THE
 WATER HEATER VENT SHALL NOT EXCEED 60 FT. PER
 MANUFACTURER' S SPECIFICATIONS- SECTION G2408.1 FBC
 RES.
  
 5) PLEASE NOTE THE RELATIVE GAS PIPE SIZING TABLES IN
 THE FBC RES FOR SINGLE FAMILY HOMES: G2413.4(1),
 G2413.4(2), AND G24133.4(5).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  