2020-06-03 09:41:16 | 4TH REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20031395 |
| 6/3/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| THE REQUIRED PLAN CORRECTIONS LISTED BELOW WERE |
| DISCUSSED IN A TELEPHONE CALL WITH THE NEW ENGINEER OF |
| RECORD- DANIEL RIVEROS PE. MR. RIVEROS WILL CORRECT THE |
| PLANS ACCORDINGLY. |
| |
| 1) SHEET G-02, GAS RISER: SHOW THE SIZE OF THE INCOMING |
| GAS PIPE TO THE METER AND PROVIDE THE CORRECT SIZING |
| TABLE FOR A 2 PSI SYSTEM- TABLE 402.4(5) FBC FG. PLEASE |
| NOTE THAT TABLE 402.4(2) IS THE SIZING TABLE FOR LESS |
| THAN 2 PSI WHICH WOULD BE THE PRESSURE DOWNSTREAM OF |
| THE REGULATOR. |
| |
| 2) G-02, GAS RISER: PROVIDE THE LENGTHS OF THE 1.2" AND |
| 3/4" BRANCH PIPES SUPPLYING THE RANGE AND THE WATER |
| HEATER FROM THE 1" TEE. PLEASE SEE TABLE 402.4(2)- THE |
| 3/4" BRANCH PIPE TO THE WATER HEATER IS UNDERSIZED AND |
| MUST BE INCREASED TO A 1" PIPE. |
| |
| 3) G-02, GAS RISER: THE SPECS FOR THE NAVIEN GAS WATER |
| HEATER INDICATE A MAXIMUM 10.5 "WC PRESSURE TO THE |
| UNIT. PLEASE PLACE A NOTE BY THE REGULATOR AND SUBMIT |
| SPECS- G2408.1 FBC RES. |
| |
| 4) G-01: PLACE A NOTE TO INDICATE THE LENGTH OF THE |
| WATER HEATER VENT SHALL NOT EXCEED 60 FT. PER |
| MANUFACTURER' S SPECIFICATIONS- SECTION G2408.1 FBC |
| RES. |
| |
| 5) PLEASE NOTE THE RELATIVE GAS PIPE SIZING TABLES IN |
| THE FBC RES FOR SINGLE FAMILY HOMES: G2413.4(1), |
| G2413.4(2), AND G24133.4(5). |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |