2020-04-28 11:09:391) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 STOVE. THE STOVE SHALL BE LISTED AND LABELED PER 2017
 FBC-FUEL GAS SEC.301.3.
 2) THE RESPONSE NARRATIVE STATES THE TANKLESS WATER
 HEATER IS 199,000 BTU'S BUT THE MANUFACTURER'S
 SPECIFICATIONS THAT HAVE BEEN SUBMITTED SHOW 180,000
 BTU'S. CLARIFY.
 3) THE RESPONSE NARRATIVE AND PLANS NOTE THE GAS
 PRESSURE IS 2 PSI WITH A PRESSURE DROP OF 0.6 WATER
 COLUMN. THERE IS NO SUCH SIZING TABLE IN THE GAS CODE.
 CLARIFY.
 4) THE SIZING TABLE NOTED IN THE RESPONSE NARRATIVE FOR
 THE CSST IS FOR A GAS SYSTEM WITH AN INLET PRESSURE OF
 5 PSI. THIS SYSTEM IS NOTED ON THE PLAN AS A 2 PSI
 SYSTEM. CLARIFY.
 5) INDICATE ON THE PLAN WHICH SIZING TABLE IS BEING
 USED FOR THE 2 PSI SYSTEM.
 6) THE INFORMATION ON THE RESPONSE NARRATIVE SHALL BE
 ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 7) A PALM BEACH COUNTY PLAN REVISION FORM HAS BEEN
 SUBMITTED WITH THIS PERMIT. CLARIFY WHY THIS FORM HAS
 BEEN SUBMITTED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  