2020-03-31 11:40:01 | 1ST REVIEW FBC-2017 FUEL GAS |
| PERMIT #20031395 |
| 3/31/20 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| PLEASE NOTE THAT ALL GAS PIPING AND APPLIANCES EITHER |
| INSTALLED UNDER THE EXPIRED PERMIT #09010132, OR ANY |
| OTHER UNPERMITTED GAS PIPING AND GAS APPLIANCE |
| INSTALLATIONS MUST BE ACCOUNTED FOR UNDER THIS NEW GAS |
| PERMIT. |
| |
| 1) THE GAS PIPING DRAWING IS INCOMPLETE AND MORE |
| INFORMATION IS REQUIRED FOR A FULL REVIEW. PLEASE |
| PROVIDE A CLEARLY DRAWN GAS PIPING ISOMETRIC DRAWING |
| THAT SHOWS THE FOLLOWING LIST OF ITEMS: |
| |
| A) TYPES OF PIPING, PIPE DIAMETERS, THE MEASUREMENTS OF |
| EACH CUT LENGTH OF PIPE, AND THE TOTAL DEVELOPED LENGTH |
| OF THE PIPING FROM THE POINT OF DELIVERY AT THE METER |
| TO THE MOST REMOTE OUTLET IN THE BUILDING- SECTION |
| G2413.4.1 & G2413.4.2 FBC RES. |
| |
| B) BTUH LOADS OF THE NEW WATER HEATER, THE EXISTING |
| STOVE, AND ANY OTHER EXISTING GAS-FIRED APPLIANCES OR |
| EQUIPMENT. SHOW THE LOAD AT EACH APPLIANCE LOCATION AND |
| THE TOTAL LOAD ON THE SYSTEM- SECTION G2413.3, |
| G24113.4, AND TABLES G2413.4(1) THROUGH G2413.4(21) FBC |
| RES. |
| |
| C) GAS DELIVERY PRESSURE (PSI) OF THE SYSTEM AT THE |
| METER AND AT EACH STEPDOWN (MP) REGULATOR- SECTION |
| G2413.2 & G2413.3 FBC RES. |
| |
| D) INDICATE WHICH SIZING TABLES WERE USED FOR THE |
| GALVANIZED PIPING AND THE CSST. PLEASE INDICATE THE |
| CORRESPONDING EHD (EQUIVALENT HYDRAULIC DIAMETER) OF |
| THE CSST AS INDICATED IN THE PIPE SIZING TABLES AND IN |
| ACCORDANCE WITH THE CSST MANUFACTURER'S SPECIFICATIONS- |
| SEE TABLES G2413.4(1) THROUGH (21). |
| |
| E) SHOW THE REQUIRED UNIONS FOR THE RIGID PIPING WITHIN |
| ONE FOOT OF THE MP REGULATORS- SECTION G2421.2(7) FBC |
| RES. |
| |
| F) ADVISORY: PLEASE NOTE THAT THE REGULATOR FOR THE |
| TANKLESS WATER HEATER MUST BE CAPABLE OF REDUCING THE |
| PRESSURE DOWN TO 10.5 " WC PER THE SUBMITTED CUT SHEET. |
| |
| 2) SUBMIT A SEPARATE FLOOR PLAN DRAWING THAT SHOWS THE |
| LOCATIONS OF ALL NEW AND EXISTING GAS-FIRED APPLIANCES |
| ON THE SYSTEM- SECTION G2406.1 & G2406.2 FBC RES. SHOW |
| THE GAS VENT AND AIR INLET DUCT RUNS THROUGH THE |
| BUILDING AND THEIR TOTAL RUN LENGTHS FOR THE WATER |
| HEATER TO THEIR EXTERIOR INLET AND OUTLET LOCATIONS. |
| INDICATE THE TYPES AND SIZES OF VENT AND AIR INLET |
| PIPINGS AND SUBMIT MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS FOR THE WATER HEATER AND THE PIPING- |
| SECTION M2005.1 & G2408.1 FBC RES. |
| |
| 3) SHOW HOW ACCESS FOR SERVICE AND REPLACEMENT OF THE |
| WEATER HEATER WILL BE PROVIDED, AND THE REQUIRED 30X30 |
| " LEVEL WORKING SPACE FOR THE APPLIANCE- SECTION |
| P2801.4 FBC RES. |
| |
| 4) INDICATE HOW CONDENSATE FOR THE TANKLESS WATER |
| HAETER WILL BE PROPERLY DISCHARGED TO THE EXTERIOR OF |
| THE BUILDING- M1411.3 FBC RES. |
| |
| 5) IF POSSIBLE PLEASE SUBMIT MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR ALL |
| UNPERMITED OR EXISTING GAS-FIRED APPLIANCES OR |
| EQUIPMENT- SECTION G2408.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |