2020-03-31 11:40:011ST REVIEW FBC-2017 FUEL GAS
 PERMIT #20031395
 3/31/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE NOTE THAT ALL GAS PIPING AND APPLIANCES EITHER
 INSTALLED UNDER THE EXPIRED PERMIT #09010132, OR ANY
 OTHER UNPERMITTED GAS PIPING AND GAS APPLIANCE
 INSTALLATIONS MUST BE ACCOUNTED FOR UNDER THIS NEW GAS
 PERMIT.
  
 1) THE GAS PIPING DRAWING IS INCOMPLETE AND MORE
 INFORMATION IS REQUIRED FOR A FULL REVIEW. PLEASE
 PROVIDE A CLEARLY DRAWN GAS PIPING ISOMETRIC DRAWING
 THAT SHOWS THE FOLLOWING LIST OF ITEMS:
  
 A) TYPES OF PIPING, PIPE DIAMETERS, THE MEASUREMENTS OF
 EACH CUT LENGTH OF PIPE, AND THE TOTAL DEVELOPED LENGTH
 OF THE PIPING FROM THE POINT OF DELIVERY AT THE METER
 TO THE MOST REMOTE OUTLET IN THE BUILDING- SECTION
 G2413.4.1 & G2413.4.2 FBC RES.
  
 B) BTUH LOADS OF THE NEW WATER HEATER, THE EXISTING
 STOVE, AND ANY OTHER EXISTING GAS-FIRED APPLIANCES OR
 EQUIPMENT. SHOW THE LOAD AT EACH APPLIANCE LOCATION AND
 THE TOTAL LOAD ON THE SYSTEM- SECTION G2413.3,
 G24113.4, AND TABLES G2413.4(1) THROUGH G2413.4(21) FBC
 RES.
  
 C) GAS DELIVERY PRESSURE (PSI) OF THE SYSTEM AT THE
 METER AND AT EACH STEPDOWN (MP) REGULATOR- SECTION
 G2413.2 & G2413.3 FBC RES.
  
 D) INDICATE WHICH SIZING TABLES WERE USED FOR THE
 GALVANIZED PIPING AND THE CSST. PLEASE INDICATE THE
 CORRESPONDING EHD (EQUIVALENT HYDRAULIC DIAMETER) OF
 THE CSST AS INDICATED IN THE PIPE SIZING TABLES AND IN
 ACCORDANCE WITH THE CSST MANUFACTURER'S SPECIFICATIONS-
 SEE TABLES G2413.4(1) THROUGH (21).
  
 E) SHOW THE REQUIRED UNIONS FOR THE RIGID PIPING WITHIN
 ONE FOOT OF THE MP REGULATORS- SECTION G2421.2(7) FBC
 RES.
  
 F) ADVISORY: PLEASE NOTE THAT THE REGULATOR FOR THE
 TANKLESS WATER HEATER MUST BE CAPABLE OF REDUCING THE
 PRESSURE DOWN TO 10.5 " WC PER THE SUBMITTED CUT SHEET.
  
 2) SUBMIT A SEPARATE FLOOR PLAN DRAWING THAT SHOWS THE
 LOCATIONS OF ALL NEW AND EXISTING GAS-FIRED APPLIANCES
 ON THE SYSTEM- SECTION G2406.1 & G2406.2 FBC RES. SHOW
 THE GAS VENT AND AIR INLET DUCT RUNS THROUGH THE
 BUILDING AND THEIR TOTAL RUN LENGTHS FOR THE WATER
 HEATER TO THEIR EXTERIOR INLET AND OUTLET LOCATIONS.
 INDICATE THE TYPES AND SIZES OF VENT AND AIR INLET
 PIPINGS AND SUBMIT MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE WATER HEATER AND THE PIPING-
 SECTION M2005.1 & G2408.1 FBC RES.
  
 3) SHOW HOW ACCESS FOR SERVICE AND REPLACEMENT OF THE
 WEATER HEATER WILL BE PROVIDED, AND THE REQUIRED 30X30
 " LEVEL WORKING SPACE FOR THE APPLIANCE- SECTION
 P2801.4 FBC RES.
  
 4) INDICATE HOW CONDENSATE FOR THE TANKLESS WATER
 HAETER WILL BE PROPERLY DISCHARGED TO THE EXTERIOR OF
 THE BUILDING- M1411.3 FBC RES.
  
 5) IF POSSIBLE PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR ALL
 UNPERMITED OR EXISTING GAS-FIRED APPLIANCES OR
 EQUIPMENT- SECTION G2408.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  