2020-04-07 16:33:5904/07/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A BETTER DETAIL PLUMBING RISER
 DIAGRAM PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (11) RESIDENTIAL PLUMBING. THE SINK AND LAVS
 ARE NOT SHOWN PROPERLY VENTED, THE WASHING MACHINE NEED
 TO BE ON A 3" DRAINAGE LINE PER MANUFACTURES
 SPECIFICATION, SEPARATE BATHROOM GROUP AND A WET VENT
 SYSTEM MAY BE A COMPLEXES DIRECTION.
  
 2. WASHING MACHINE VALVES NEED TO BE ACCESSIBLE WITHOUT
 MOVING THE UNIT, THEY MAY BE ON THE SIDE, A NOTE WILL
 BE SUFFICIVE ON PLANS REFERRING TO 2017 PER THE
 2903.9.3.
  
 3. PLEASE SHOW THE SOURCE OF HOT WATER AND LOCATION PER
 THE 2017 FBC SEC R 2722.2.
  
 4. PLEASE IDENTIFY YOUR VENT LINE THROUGH THE ROOF AS
 DASH LINE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  