2020-04-01 10:56:03 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| 2.LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE |
| FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(D); |
| FBC RE E4003.11 |
| 3.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| 4.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE |
| EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). |
| SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC |
| 107.2.1 |
| 5.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC |
| 107.2.1 |
| 6.SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC |
| 210.52; FBC RE E3901.2.1 |
| 7.IDENTIFY OLD AND NEW WORK |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| PHIL PETTY |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6742 |
| [email protected] |
| |