Plan Review Notes
Plan Review Notes For Permit 20031386
Permit Number 20031386
Review Stop B
Sequence Number 1
Notes
Date Text
2020-03-31 10:36:26PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107.2.1, PROVIDE THE EMBEDMENT DEPTH OF THE
 INTERIOR AND EXTERIOR COLUMN ANCHOR BOLTS.
 2) FBC B 107.2.1, PROVIDE THE SIZE AND QUANTITY OF
 FASTENERS FOR THE COLUMN SPLIT PLATE CONNECTIONS TO THE
 BEAMS ABOVE AT BOTH INTERIOR AND EXTERIOR COLUMNS.
 3) FBC B 107.2.1, PROVIDE CONCRETE/BLOCK WALL
 REINFORCEMENT DETAIL FOR AREA BELOW NEW BEAM SUPPORTING
 POCKETS AT KITCHEN AND BEDROOM #3 EXTERIOR WALLS.
 4) FBC B 107, PROVIDE ROOFING DETAILS FOR UNDER
 ELEVATED BALCONY DECKING.
 5) FBC B 107, PROVIDE ALL PRODUCT APPROVALS FOR
 WINDOWS, DOORS, AND ROOFING MATERIALS.
 6) FBC B 310, THE OCCUPANCY CLASSIFICATION INDICATED ON
 THE PLANS IS R-3 BUT IT APPEARS THAT THIS OCCUPANCY
 CLASSIFICATION IS R-2 PER THE FLORIDA BUILDING CODE.
 PLEASE ADJUST ON PLANS AND CLARIFY.
  
 NOTE: A ROOFING SUB-PERMIT IS REQUIRED.