Plan Review Notes For Permit 20031386 |
Permit Number |
20031386 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-03-31 10:36:26 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | 1) FBC B 107.2.1, PROVIDE THE EMBEDMENT DEPTH OF THE | | INTERIOR AND EXTERIOR COLUMN ANCHOR BOLTS. | | 2) FBC B 107.2.1, PROVIDE THE SIZE AND QUANTITY OF | | FASTENERS FOR THE COLUMN SPLIT PLATE CONNECTIONS TO THE | | BEAMS ABOVE AT BOTH INTERIOR AND EXTERIOR COLUMNS. | | 3) FBC B 107.2.1, PROVIDE CONCRETE/BLOCK WALL | | REINFORCEMENT DETAIL FOR AREA BELOW NEW BEAM SUPPORTING | | POCKETS AT KITCHEN AND BEDROOM #3 EXTERIOR WALLS. | | 4) FBC B 107, PROVIDE ROOFING DETAILS FOR UNDER | | ELEVATED BALCONY DECKING. | | 5) FBC B 107, PROVIDE ALL PRODUCT APPROVALS FOR | | WINDOWS, DOORS, AND ROOFING MATERIALS. | | 6) FBC B 310, THE OCCUPANCY CLASSIFICATION INDICATED ON | | THE PLANS IS R-3 BUT IT APPEARS THAT THIS OCCUPANCY | | CLASSIFICATION IS R-2 PER THE FLORIDA BUILDING CODE. | | PLEASE ADJUST ON PLANS AND CLARIFY. | | | | NOTE: A ROOFING SUB-PERMIT IS REQUIRED. |
|