Plan Review Notes
Plan Review Notes For Permit 20031380
Permit Number 20031380
Review Stop P
Sequence Number 1
Notes
Date Text
2020-04-02 09:59:581) SUBMIT CALCULATIONS FOR THE RAINWATER SYSTEM.
 FPC-PLUMBING SEC.1105.2, 1106.1.
 2) SHT. P 101 NOTES " REFER TO CIVIL." THERE ARE NO
 CIVIL PLANS IN THIS SUBMITTAL. CLARIFY.
 3) ANY HOT WATER LINE BELOW THE SLAB SHALL BE INSULATED
 PER FL. ENERGY CODE.
 4) A BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED ON
 THE WATER SUPPLY TO THE DISHWASHER PER FBC-PLUMBING
 SEC. 608.2, 608.3.
 5) A GREASE TRAP WILL BE REQUIRED TO COLLECT THE WASTES
 FROM THE SINKS.FBC-PLUMBING SEC.1003.1
 6) THE FLOOR SINKS SHALL BE VENTED PER FBC-PLUMBING
 SEC. 901.2, 901.2.1. AN AIR ADMITTANCE VALVE CANNOT BE
 USED AS NOT LESS THAN ONE STACK VENT OR VENT STACK
 SHALL EXTEND OUTDOORS TO THE OPEN AIR. FBC-PLUMBING
 SEC. 918.7.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  