Plan Review Notes For Permit 20031380 |
Permit Number |
20031380 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-04-02 09:59:58 | 1) SUBMIT CALCULATIONS FOR THE RAINWATER SYSTEM. | | FPC-PLUMBING SEC.1105.2, 1106.1. | | 2) SHT. P 101 NOTES " REFER TO CIVIL." THERE ARE NO | | CIVIL PLANS IN THIS SUBMITTAL. CLARIFY. | | 3) ANY HOT WATER LINE BELOW THE SLAB SHALL BE INSULATED | | PER FL. ENERGY CODE. | | 4) A BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED ON | | THE WATER SUPPLY TO THE DISHWASHER PER FBC-PLUMBING | | SEC. 608.2, 608.3. | | 5) A GREASE TRAP WILL BE REQUIRED TO COLLECT THE WASTES | | FROM THE SINKS.FBC-PLUMBING SEC.1003.1 | | 6) THE FLOOR SINKS SHALL BE VENTED PER FBC-PLUMBING | | SEC. 901.2, 901.2.1. AN AIR ADMITTANCE VALVE CANNOT BE | | USED AS NOT LESS THAN ONE STACK VENT OR VENT STACK | | SHALL EXTEND OUTDOORS TO THE OPEN AIR. FBC-PLUMBING | | SEC. 918.7. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|