Plan Review Notes
Plan Review Notes For Permit 20031308
Permit Number 20031308
Review Stop E
Sequence Number 1
Notes
Date Text
2020-04-28 16:25:26PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A CODE COMPLIANT ELECTRICAL PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE A NEW LOAD CALCULATION. INCLUDE ALL EXISTING
 AND PROPOSED LOADS.
 PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS
 FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR
 THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2.
  
  
  
  