2020-05-08 11:57:41CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AIC RATING OF TRANSFORMER FROM POWER
 COMPANY.
  
 PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM
 UTILITY.
  
 E3404.2 INTERRUPTING RATING.
  
 EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS
 SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000
 AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT
 LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9)
  
 AIC RATING OF SERVICE DISCONNECT AND PANEL
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
  
  
 2. PROVIDE INTERSYSTEM BONDING CONNECTION AT SERVICE.
  
 PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 3. PANEL SIZE CALCULATION FOR PANEL B USES INCORRECT
 KVA. TOTAL PANEL KVA IS 2.2 KVA. PANEL SIZE CALCULATION
 USES 18.7 KVA.
  
 PLEASE CORRECT.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. HIGH EFFICACY LAMPS.
  
 PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS".
 A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1
  
 5. OUTLET IN POWDER ROOM APPEARS TO EXCEED THE 36 INCH
 MINIMUM REQUIREMENT PER E3901.6.
  
 PLEASE VERIFY
  
 6. OUTLETS FOR GARAGE DOOR OPENERS MISSING FROM PLAN.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  