2020-05-08 11:57:41 | CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| PLAN REVIEW - ELECTRICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER ? BUILDING - PX3169 |
| PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE AIC RATING OF TRANSFORMER FROM POWER |
| COMPANY. |
| |
| PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM |
| UTILITY. |
| |
| E3404.2 INTERRUPTING RATING. |
| |
| EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS |
| SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 |
| AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT |
| LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN |
| INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT |
| LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9) |
| |
| AIC RATING OF SERVICE DISCONNECT AND PANEL |
| FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM |
| FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT |
| NOT LESS THAN 10,000 AMPERES. (110.9) |
| |
| |
| 2. PROVIDE INTERSYSTEM BONDING CONNECTION AT SERVICE. |
| |
| PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| |
| 3. PANEL SIZE CALCULATION FOR PANEL B USES INCORRECT |
| KVA. TOTAL PANEL KVA IS 2.2 KVA. PANEL SIZE CALCULATION |
| USES 18.7 KVA. |
| |
| PLEASE CORRECT. |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. HIGH EFFICACY LAMPS. |
| |
| PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". |
| A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 |
| |
| 5. OUTLET IN POWDER ROOM APPEARS TO EXCEED THE 36 INCH |
| MINIMUM REQUIREMENT PER E3901.6. |
| |
| PLEASE VERIFY |
| |
| 6. OUTLETS FOR GARAGE DOOR OPENERS MISSING FROM PLAN. |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |
| |
| |