2020-05-07 16:00:37 | CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| PLAN REVIEW - BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER ? BUILDING - PX3169 |
| PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE SURVEY. |
| PROVIDE SITE PLAN. ? DRAINAGE/SURVEY |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED ON A BOUNDARY LINE SURVEY. |
| |
| 2. PROVIDE SOILS REPORT. |
| FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE |
| CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND |
| REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE |
| REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL |
| INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY |
| TESTING OR ENGINEERING CALCULATIONS, SUCH |
| INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED |
| DESIGN PROFESSIONAL. |
| |
| 3. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS AND |
| EXTERIOR DOORS. |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. |
| |
| 4. PROVIDE ICC ES EVALUATION REPORT FOR ICYNENE ATTIC |
| INSULATION. INDICATE WHAT SYSTEM WILL BE INSTALLED. A |
| COPY OF THE INSTALLATION INSTRUCTIONS SHALL BE ON-SITE |
| FOR THE CITY INSPECTOR. |
| |
| 5. RESIDENTIAL ELEVATORS SHALL COMPLY WITH FBC SECTION |
| 3013. |
| PROVIDE A STRUCTURAL DETAIL FOR ELEVATOR SHAFT. |
| PROVIDE STRUCTURAL CONNECTION DETAIL FOR ELEVATOR TO |
| STRUCTURE. |
| PROVIDE MANUFACTURERS SPECIFICATIONS. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |