2020-05-04 15:46:54 | PLAN REVIEW - ELECTRICAL |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER ? BUILDING - PX3169 |
| PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. REMOVED - CT |
| |
| 2. LUMINAIRES INSTALLED IN SHOWER AREAS REQUIRED TO BE |
| VAPOR PROOF. |
| |
| VAPOR PROOF LIGHTING |
| E4003.9 WET OR DAMP LOCATIONS. |
| LUMINAIRES INSTALLED IN WET OR DAMP LOCATIONS SHALL BE |
| INSTALLED SO THAT WATER CANNOT ENTER OR ACCUMULATE IN |
| WIRING COMPARTMENTS, LAMP HOLDERS OR OTHER ELECTRICAL |
| PARTS. ALL LUMINAIRES INSTALLED IN WET LOCATIONS SHALL |
| BE MARKED SUITABLE FOR WET LOCATIONS. ALL LUMINAIRES |
| INSTALLED IN DAMP LOCATIONS SHALL BE MARKED SUITABLE |
| FOR WET LOCATIONS OR SUITABLE FOR DAMP LOCATIONS. |
| (410.10) |
| |
| INCLUDE VP NEXT TO THE SYMBOL AT THE VAPOR PROOF |
| FIXTURE IN THE SHOWER AREA. |
| |
| 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER AT THE PANEL FOR THE SUB-PANELS AT THE |
| PROPOSED ADDITION. NEC 225.31, 225.32 |
| |
| 4. REMOVED - CT |
| |
| 5. REMOVED - CT |
| |
| 6. A NOTICE SHALL BE POSTED ON THE ELECTRIC SERVICE |
| PANEL INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER |
| IS LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST |
| PARAGRAPH IN BOLD PER R403.3.6. |
| |
| 7. THE OUTLET SHOWN BETWEEN THE TWO MASTER BATH BASIN |
| SHALL BE GFCI PROTECTED. |
| |
| |
| |
| |
| |