Plan Review Notes For Permit 20031252 |
Permit Number |
20031252 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-03-27 09:41:05 | REVISION BUILDING REVIEW COMMENTS. | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- BASED ON THE INFORMATION SUBMITTED, THIS IS NOT A | | REVISION TO A RE-ROOFING PERMIT. DRAWINGS SUBMITTED | | SHOW WHAT IT LOOKS LIKE THE CONVERSION OF A ROOF DECK | | INTO AN OCCUPIABLE ROOF DECK. IT SHOWS A NEW DECK AND | | RAILING ON TOP OF EXISTING ROOF. | | NEED TO PROVIDE COMPLETE INFORMATION UNDER A SEPARATE | | PERMIT. SEC. 105.1 CITY AMENDMENTS. | | | | 2- NEED TO PROVIDE COMPLETE SET OF DRAWINGS (TWO SETS) | | PERFORMED BY A LICENSED DESIGN PROFESSIONAL SHOWING THE | | DESIGN FOR THE PROPOSED USE. SEC. 107.1 AND 107.2.1 | | CITY AMENDMENTS. | | | | 3-THIS WORK CAN NOT BE DONE BY A ROOFING CONTRACTOR, | | UNLESS THE ROOFING CONTRACTOR HAS A LICENSE TO PERFORM | | STRUCTURAL WORK. SEC. 489.105 F.S. NEED COMPLETE PERMIT | | APPLICATION BY QUALIFIED CONTRACTOR. COORDINATE WITH | | ITEM #1 ABOVE. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|