Plan Review Notes
Plan Review Notes For Permit 20031238
Permit Number 20031238
Review Stop B
Sequence Number 2
Notes
Date Text
2020-03-27 14:24:16RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL10497-R6
 SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 JAMES SHEPARD LEFT ME A MESSAGE STATING THAT HE'S
 INSTALLING ASSEMBLY W-1. THIS IS A BONDED INSULATION
 AND BONDED ROOF COVER ASSEMBLY. THE MAXIMUM DESIGN
 PRESSURE FOR THIS ASSEMBLY IS -52.5. THIS ASSEMBLY CAN
 NOT BE USED BECAUSE IT DOESN'T MEET THE DESIGN PRESSURE
 FOR ALL ROOF ZONES AND NOT RATIONAL ANALYSIS IS ALLOWED
 FOR FULLY BONDED ASSEMBLIES. SEE LIMITATION #5.8 ON
 PAGE 4 OF 5 OF PRODUCT APPROVAL SUBMITTED.
 NEED TO SELECT ANOTHER ASSEMBLY THAT MEETS THE DESIGN
 PRESSURE FOR ALL ROOF ZONES OR THAT ALLOWS RATIONAL
 ANALYSIS (USUALLY RAS 117 CALCULATIONS).
  
 2- PROVIDE COMPLETE FLAT ROOF FLORIDA PRODUCT APPROVAL.
 PRODUCT APPROVAL SUBMITTED IS MISSING THE FLORIDA
 PRODUCT APPROVAL COVER PAGE. THIS PAGE IS REQUIRED
 BECAUSE IT SHOWS THE CURRENT CODE VERSION AND THE
 PRODUCT APPROVAL STATUS. CHAPTER 553 F.S. AND FAC
 61G20-3.001.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]