Plan Review Notes For Permit 20031238 |
Permit Number |
20031238 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-03-26 17:31:35 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK | | SHALL COMPLY WITH THE MATERIALS AND METHODS | | REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL10497-R6 | | SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS | | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: | | IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | 2- PROVIDE COMPLETE FLAT ROOF FLORIDA PRODUCT APPROVAL. | | PRODUCT APPROVAL SUBMITTED IS MISSING THE FLORIDA | | PRODUCT APPROVAL COVER PAGE. THIS PAGE IS REQUIRED | | BECAUSE IT SHOWS THE CURRENT CODE VERSION AND THE | | PRODUCT APPROVAL STATUS. CHAPTER 553 F.S. AND FAC | | 61G20-3.001. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|