Plan Review Notes
Plan Review Notes For Permit 20031229
Permit Number 20031229
Review Stop G
Sequence Number 6
Notes
Date Text
2020-07-20 10:47:325TH REVIEW FBC-2017 RES. FUEL GAS
 PERMIT #20031229
 7/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE PREVIOUS REVIEWS LISTED BELOW HAVE
 NOT BEEN ADDRESSED ON THE PLANS AND NO NARRATIVE
 RESPONSE WAS PROVIDED.
 ON THE DATE OF THIS REVIEW- 7/20/17- I CONTACTED THE
 COMPANY BY TELEPHONE, AND THE COMPANY HAS AGREED TO
 PROVIDE THE CORRECTIONS ON THE NEXT SUBMITTAL.
  
 1) THE SUBMITTED GAS RISER DRAWING BY C & C DIVERSIFIED
 SERVICES WAS ORIGINALLY SUBMITTED UNDER PERMIT 19040921
 WHICH IS STILL AN OPEN PERMIT. TO DATE NO GAS
 INSPECTIONS HAVE BEEN PERFORMED UNDER THAT PERMIT. IF C
 & C DIVERSIFIED SERVICES TO BE THE SUB-CONTRACTOR UNDER
 THIS GENERATOR PERMIT, THEN A NEW SUB-PERMIT IS
 REQUIRED. IF MITCHELL MECHANICAL & ELECTRICAL REMAINS
 THE SUB THEN A NEW GAS RISER PLAN SHALL BE SUBMITTED
 AND SIGNED BY MITCHELL MECHANICAL AND ELECTRICAL-
 SECTIONS 105.3 AND 107.2.1 WPB.
  
 2) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED
 GENERATOR SPECS INDICATE THE GENERATOR HAS A GAS LOAD
 OF 1,202,000 BTUH AT 100% CAPACITY. PLEASE CORRECT THE
 LOAD ON THE NEW RISER DRAWING- SECTION 107.2.1 WPB.
  
 3) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED RISER
 DRAWING SHOWS A NEW REGULATOR FOR THE INTERIOR
 GAS-FIRED APPLIANCES WITH A GAS LOAD ESTIMATED AT
 150,000 BTUH. THE NEW RISER SHALL SHOW THE LENGTH OF
 THE SYSTEM FROM THE REGULATOR TO THE MOST REMOTE
 APPLIANCE- SECTION G2413.4.1 FBC RES; SHOW THE DIAMETER
 OF THE NEW 3' PIPE FROM THE METER TO THE REGULATOR, AND
 INDICATE THE SIZING TABLE USED FOR THE SYSTEM- SECTION
 2413.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  