2020-07-01 16:01:29 | 4TH REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT #20031229 |
| 6/16/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENTS FROM THE PREVIOUS REVIEWS LISTED BELOW HAVE |
| NOT BEEN ADDRESSED ON THE PLANS AND NO NARRATIVE |
| RESPONSE WAS PROVIDED. |
| |
| 1) THE SUBMITTED GAS RISER DRAWING BY C & C DIVERSIFIED |
| SERVICES WAS ORIGINALLY SUBMITTED UNDER PERMIT 19040921 |
| WHICH IS STILL AN OPEN PERMIT. TO DATE NO GAS |
| INSPECTIONS HAVE BEEN PERFORMED UNDER THAT PERMIT. IF C |
| & C DIVERSIFIED SERVICES TO BE THE SUB-CONTRACTOR UNDER |
| THIS GENERATOR PERMIT, THEN A NEW SUB-PERMIT IS |
| REQUIRED. IF MITCHELL MECHANICAL & ELECTRICAL REMAINS |
| THE SUB THEN A NEW GAS RISER PLAN SHALL BE SUBMITTED |
| AND SIGNED BY MITCHELL MECHANICAL AND ELECTRICAL- |
| SECTIONS 105.3 AND 107.2.1 WPB. |
| |
| 2) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED |
| GENERATOR SPECS INDICATE THE GENERATOR HAS A GAS LOAD |
| OF 1,202,000 BTUH AT 100% CAPACITY. PLEASE CORRECT THE |
| LOAD ON THE NEW RISER DRAWING- SECTION 107.2.1 WPB. |
| |
| 3) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED RISER |
| DRAWING SHOWS A NEW REGULATOR FOR THE INTERIOR |
| GAS-FIRED APPLIANCES WITH A GAS LOAD ESTIMATED AT |
| 150,000 BTUH. THE NEW RISER SHALL SHOW THE LENGTH OF |
| THE SYSTEM FROM THE REGULATOR TO THE MOST REMOTE |
| APPLIANCE- SECTION G2413.4.1 FBC RES; SHOW THE DIAMETER |
| OF THE NEW 3' PIPE FROM THE METER TO THE REGULATOR, AND |
| INDICATE THE SIZING TABLE USED FOR THE SYSTEM- SECTION |
| 2413.3 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |