Plan Review Notes For Permit 20031229 |
Permit Number |
20031229 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-05-20 12:47:06 | 1ST REVIEW FBC-2017 PLUMBING | | PERMIT #20031229 | | 5/20/2020 | | | | CODES IN EFFECT: | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE NEW GAS ISOMETRIC DRAWING SHOWS TWO INTERIOR | | TANKLESS WATER HEATERS THAT ARE NOT LABELED AS EXISTING | | ON THE DRAWING. IT APPEARS THESE WILL BE NEW | | INSTALLATIONS. PLEASE SUBMIT MANUFACTURER'S | | SPECIFICATIONS AND INSTALLATION GUIDELINES FOR THE | | UNITS- SEE SECTIONS P2801.3 AND G2408.1 FBC RES. PLEASE | | NOTE THAT A PLUMBING SUB-PERMIT MUST BE SUBMITTED- | | SECTION 105.3 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|