Plan Review Notes
Plan Review Notes For Permit 20031229
Permit Number 20031229
Review Stop E
Sequence Number 1
Notes
Date Text
2020-04-01 16:05:08ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO ELECTRICAL PLANS SUBMITTED.
  
 2) RISER DIAGRAM REQUIRED FOR SERVICE PROVIDE RISER
 DIAGRAM OF EXISTING SERVICE. NEC 215.5; FBC 107.2.1
  
 3) PROVIDE LOAD CALCULATION. PROVIDE ACCURATE LOAD
 CALCULATION INCLUDING ALL LOADS. NEC 220; FBC RE3602.3
  
 4) HAVE NO IDEA WHAT SIZE GENERATOR IS BEING INSTALLED,
 TRANSFER SWITCH (SE RATED OR NOT).
  
 5) DEPENDING ON THE SIZE OF THE GENERATOR AND TRANSFER
 SWITCH VALUE MAY BE A QUESTION (YOU CAN INCLUDE
 CONTRACT ON RESUBMITAL IF YOU LIKE.)
  
 6) SUMITTED PLANS SHALL BE SIGNED BY THE ELECTRICAL
 QUALIFIER. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
  