Plan Review Notes
Plan Review Notes For Permit 20031189
Permit Number 20031189
Review Stop E
Sequence Number 1
Notes
Date Text
2020-03-31 08:36:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHOW COMPLIANCE WITH FBCR - E 4204.2 FOR
 EQUIPOTENTIAL BONDING.
  
 2) THE FEEDERS FROM THE BUILDING ELECTRICAL PANEL TO
 THE 125 AMP POOL PANEL ARE UNDERSIZED. NEC 310.15
  
 NOTE: SEPARATE PERMIT IS REQUIRED FOR THE ELECTRICAL
 SERVICE CHANGE.
  
 END OF COMMENTS.
  