2020-03-27 14:36:23CHANGE OF OCCUPANCY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) JOB APPEARS TO BE A CHANGE OF OCCUPANCY FROM AN R2
 TO AN ALF WHICH MAYBE R4 OR I - PLEASE CLARIFY - SEE
 FBC CHAPTER 3.
 2) PLEASE SHOW FIRE RATED WALLS BETWEEN UNITS TO COMPLY
 WITH FBC 420.2
 3) PLEASE SHOW THE FIRE RATED "HORIZONTAL SEPARATION"
 FROM THE UNIT ABOVE TO COMPLY WITH FBC 420.3
 4) PLEASE SHOW THE NUMBER OF PERSONS TO OCCUPY THE
 BUILDING.
 5) PLEASE SHOW THAT THE BUILDING HAS OR ADDING FIRE
 SPRINKLERS TO COMPLY WITH FBC 420.5
 6) DRAWING A2 SHOWS WIND LOAD PER FBC 1606 - SHOULD BE
 FBC 1609 (WIND SPEED 170MPH AND ASCE 7-10)
 7) DOOR NUMBER 1 IS NOT SHOWN ON THE DOOR SCHEDULE.
 8) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE NEW EXTERIOR WINDOWS AND
 DOORS.
 THIS MAY NOT BE A COMPLETE LIST OF REQUIREMENTS THE
 OCCUPANCY CLASSIFICATION HAS NOT BEEN DETERMINED.
  
  