Plan Review Notes For Permit 20031184 |
Permit Number |
20031184 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-03-27 14:36:23 | CHANGE OF OCCUPANCY | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - | | 1) JOB APPEARS TO BE A CHANGE OF OCCUPANCY FROM AN R2 | | TO AN ALF WHICH MAYBE R4 OR I - PLEASE CLARIFY - SEE | | FBC CHAPTER 3. | | 2) PLEASE SHOW FIRE RATED WALLS BETWEEN UNITS TO COMPLY | | WITH FBC 420.2 | | 3) PLEASE SHOW THE FIRE RATED "HORIZONTAL SEPARATION" | | FROM THE UNIT ABOVE TO COMPLY WITH FBC 420.3 | | 4) PLEASE SHOW THE NUMBER OF PERSONS TO OCCUPY THE | | BUILDING. | | 5) PLEASE SHOW THAT THE BUILDING HAS OR ADDING FIRE | | SPRINKLERS TO COMPLY WITH FBC 420.5 | | 6) DRAWING A2 SHOWS WIND LOAD PER FBC 1606 - SHOULD BE | | FBC 1609 (WIND SPEED 170MPH AND ASCE 7-10) | | 7) DOOR NUMBER 1 IS NOT SHOWN ON THE DOOR SCHEDULE. | | 8) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVAL FOR THE NEW EXTERIOR WINDOWS AND | | DOORS. | | THIS MAY NOT BE A COMPLETE LIST OF REQUIREMENTS THE | | OCCUPANCY CLASSIFICATION HAS NOT BEEN DETERMINED. | | | | |
|