2020-04-03 05:56:39 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20031182 |
| ADD: 512 BAKER DR. |
| CONT: MONICA ROSSI CONSTRUCTION |
| TEL: 561-270-9242 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| CODE 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL |
| NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MONDAY MARCH 30/2020 |
| ACTION: DENIED |
| |
| 1) THE VALUE FOR THE REMOVAL, DISPOSAL OF 2 DOORS, |
| PURCHASING 2 DOORS AND INSTALLATION OF THE 2 DOORS IS |
| EXTREMELY LOW. |
| W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1 ADMINISTRATIVE CODE 108.3* |
| BUILDING PERMIT VALUATION. IF, IN THE OPINION OF THE |
| BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR |
| PLUMBING SYSTEMS APPEARS TO BE UNDER ESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| 2) 107.3.5. MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| MISSING FLOOR PLAN SHOWING THE LOCATION OF THE EXTERIOR |
| DOORS THAT ARE BEING REPLACED. ALSO INDICATE ROOM USAGE |
| ON THE FLOOR PLAN. PROVIDE THE SIZE OF THE DOOR AND |
| DISTANCE FROM THE CORNER OF THE DWELLING UNIT. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIED. |
| |
| 3) 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE |
| THE EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR TO BE LICENSED IN |
| THE TRADE THAT THEY WILL BE CREATING THE PLANS TO BE |
| SUBMITTED TO THE BUILDING DEPARTMENT. FOR EACH TRADE |
| THE CONTRACTOR RESPONSIBLE FOR THE PLAN MUST PRINT |
| THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER. |
| |
| 4) MISSING WIND DESIGN CRITERIA. 2017 FBC-B 1603.1.4 |
| WIND DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO |
| WIND LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND |
| LOADS GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING |
| SYSTEM OF THE STRUCTURE: |
| |
| 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 4.2. RISK CATEGORY. |
| |
| 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. |
| |
| 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 4.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| |
| 5) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & SIDELIGHTS. |
| |
| 6) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 7) THE SUBMITTED PRODUCT APPROVAL 4940-R7 MASONITE |
| INTERNATIONAL ONLY HAS THE COVER SHEETS 1-3 SUBMITTED. |
| NONE OF THE 5 SUB-SYSTEMS ARE HIGHLIGHTED AND NONE OF |
| THE TECHNICAL SHEETS WERE LOADED. A THROUGH PLAN REVIEW |
| COULD NOT BE COMPLETED AT THIS TIME BECAUSE OF THE |
| MISSING DOCUMENTS. |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, SFP & CBO |