Plan Review Notes For Permit 20031121 |
Permit Number |
20031121 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-04-13 07:17:19 | REVIEW FBC-2017 MECHANICAL | | PERMIT-20031121 | | | | CODES IN EFFECT: | | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | THE NEW MANUAL J CALCULATIONS DO NOT MATCH THE DRAWING | | THAT WAS SUBMITTED. THE MANUAL J CALCULATIONS SPECS. | | OUT 1 5-TON UNIT WITH DUCT WORK FROM THIS 1 SYSTEM | | THROUGH OUT THE HOUSE. THE DRAWING SHOWS 3 SEPARATE | | SYSTEMS. PLEASE SUBMIT DOCUMENTS THAT MATCH. FBC FS | | 107.2.1 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | |
|