Plan Review Notes
Plan Review Notes For Permit 20031119
Permit Number 20031119
Review Stop P
Sequence Number 2
Notes
Date Text
2020-05-07 13:15:54REVIEWED BY JERRY SMITH.
  
 PLUMBING COMMENTS: APPROVED WITH PROVISO
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PLUMBING PROVISO
 I. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, A REVISED PLAN SHEET A7 WHICH
 SHALL PROVIDE THE INFORMATION NOTED BELOW.
 1. A7 INTERIOR ELEVATIONS; DETAILS 5 AND 6:
 A. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 B. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3
  
 2. A7 INTERIOR ELEVATIONS; DETAILS 5, 6 AND 7:
 A. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE PER FBC ACC 609.4
 B. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
  
 3. A7 INTERIOR ELEVATIONS; DETAIL 7:
 A. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 B. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
  
 DOCUMENT SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR
 TO FIRST INSPECTION. PROCEED AT YOUR OWN RISK.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20031119 525 S FLAGLER DR FL 2
  
  
  
  
  
 PHONE 561-805-6715
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 PLUMBING COMMENTS: APPROVED WITH PROVISO
  
  
 PLUMBING COMMENTS: DENIED
  
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
  
 FBC EB = FBC EXISTING BUILDING
  
 FBC A = FBC ACCESSIBILITY
  
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC R = FBC RESIDENTIAL
  
 FBC M = FBC MECHANICAL
  
 FBC P = FBC PLUMBING
  
  
  
 1. 2017 FBC 107.2.1 PROVIDE SUBMITTAL SHEET FOR
  
 TANKLESS WATER HEATER CONFIRMING HEATER MEETS ENERGY
  
 CODE.
  
 2. 2017 FBC ACCESSIBILITY. PROVIDE DIMENSIONED ENLARGED
  
 TOILET ROOM ELEVATIONS. THESE ELEVATIONS ONLY SAY ADA
  
 COMPLIANT BUT PROVIDE NO DIMENSIONAL INFORMATION FOR
  
 ANY FIXTURES, GRAB BARS, MIRRORS, ETC.
  
 3. 2017 FPC PIPING SIZING. PLUMBING KEY NOTE 1 LEAVES
  
 IT TO THE CONTRACTOR TO DECIDE IF EXISTING WATER PIPE
  
 IS LARGE ENOUGH TO SUPPLY NEW LAYOUT ADEQUATELY. THIS
  
 IS A REQUIREMENT THAT NEEDS TO BE PROVIDED ON THE
  
 PLUMBING DOCUMENTS AND THE CORRECT SIZE NEEDS TO BE
  
 SHOWN ON THE NEXT SUBMITTAL.
  
  
  
 PLEASE PROVIDE A COMMENT/RESPONSE LETTER WITH YOUR
  
 RESUBMITTAL.
  
  
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
  