Date |
Text |
2020-05-07 13:15:54 | REVIEWED BY JERRY SMITH. |
| |
| PLUMBING COMMENTS: APPROVED WITH PROVISO |
| |
| ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| INSPECTOR'S APPROVAL |
| BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE |
| COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN |
| PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM |
| THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND |
| NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF |
| PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY |
| ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM |
| REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES |
| / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO |
| AVOID VOIDING OF THE PERMIT. |
| |
| PLUMBING PROVISO |
| I. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE |
| AS A DEFERRED SUBMITTAL, A REVISED PLAN SHEET A7 WHICH |
| SHALL PROVIDE THE INFORMATION NOTED BELOW. |
| 1. A7 INTERIOR ELEVATIONS; DETAILS 5 AND 6: |
| A. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| B. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| ACC 603.3 |
| |
| 2. A7 INTERIOR ELEVATIONS; DETAILS 5, 6 AND 7: |
| A. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| OF THE GRIPPING SURFACE PER FBC ACC 609.4 |
| B. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER |
| FBC ACC 604.4. |
| |
| 3. A7 INTERIOR ELEVATIONS; DETAIL 7: |
| A. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| WALL PER FBC ACC 604.5.1 |
| B. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| ACC 604.8. |
| |
| DOCUMENT SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR |
| TO FIRST INSPECTION. PROCEED AT YOUR OWN RISK. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20031119 525 S FLAGLER DR FL 2 |
| |
| |
| |
| |
| |
| PHONE 561-805-6715 |
| PLUMBING COMMENTS: APPROVED |
| ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| INSPECTOR'S APPROVAL |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| PLUMBING COMMENTS: APPROVED WITH PROVISO |
| |
| |
| PLUMBING COMMENTS: DENIED |
| |
| |
| AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN |
| SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE |
| DESIGNER PER WPB FBC 107.2.1. |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| |
| FBC EB = FBC EXISTING BUILDING |
| |
| FBC A = FBC ACCESSIBILITY |
| |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| FBC R = FBC RESIDENTIAL |
| |
| FBC M = FBC MECHANICAL |
| |
| FBC P = FBC PLUMBING |
| |
| |
| |
| 1. 2017 FBC 107.2.1 PROVIDE SUBMITTAL SHEET FOR |
| |
| TANKLESS WATER HEATER CONFIRMING HEATER MEETS ENERGY |
| |
| CODE. |
| |
| 2. 2017 FBC ACCESSIBILITY. PROVIDE DIMENSIONED ENLARGED |
| |
| TOILET ROOM ELEVATIONS. THESE ELEVATIONS ONLY SAY ADA |
| |
| COMPLIANT BUT PROVIDE NO DIMENSIONAL INFORMATION FOR |
| |
| ANY FIXTURES, GRAB BARS, MIRRORS, ETC. |
| |
| 3. 2017 FPC PIPING SIZING. PLUMBING KEY NOTE 1 LEAVES |
| |
| IT TO THE CONTRACTOR TO DECIDE IF EXISTING WATER PIPE |
| |
| IS LARGE ENOUGH TO SUPPLY NEW LAYOUT ADEQUATELY. THIS |
| |
| IS A REQUIREMENT THAT NEEDS TO BE PROVIDED ON THE |
| |
| PLUMBING DOCUMENTS AND THE CORRECT SIZE NEEDS TO BE |
| |
| SHOWN ON THE NEXT SUBMITTAL. |
| |
| |
| |
| PLEASE PROVIDE A COMMENT/RESPONSE LETTER WITH YOUR |
| |
| RESUBMITTAL. |
| |
| |
| |
| REVIEWED REMOTELY BY JAMES BAKER, PE |
| |