2020-03-27 13:24:52 | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC P = FBC PLUMBING | | | | 1. 2017 FBC 107.2.1 PROVIDE SUBMITTAL SHEET FOR | | TANKLESS WATER HEATER CONFIRMING HEATER MEETS ENERGY | | CODE. | | 2. 2017 FBC ACCESSIBILITY. PROVIDE DIMENSIONED ENLARGED | | TOILET ROOM ELEVATIONS. THESE ELEVATIONS ONLY SAY ADA | | COMPLIANT BUT PROVIDE NO DIMENSIONAL INFORMATION FOR | | ANY FIXTURES, GRAB BARS, MIRRORS, ETC. | | 3. 2017 FPC PIPING SIZING. PLUMBING KEY NOTE 1 LEAVES | | IT TO THE CONTRACTOR TO DECIDE IF EXISTING WATER PIPE | | IS LARGE ENOUGH TO SUPPLY NEW LAYOUT ADEQUATELY. THIS | | IS A REQUIREMENT THAT NEEDS TO BE PROVIDED ON THE | | PLUMBING DOCUMENTS AND THE CORRECT SIZE NEEDS TO BE | | SHOWN ON THE NEXT SUBMITTAL. | | | | PLEASE PROVIDE A COMMENT/RESPONSE LETTER WITH YOUR | | RESUBMITTAL. | | | | REVIEWED REMOTELY BY JAMES BAKER, PE | | PX3997, PE77268 | | 561-805-6724 | | [email protected] | | | | |
|