Plan Review Notes
Plan Review Notes For Permit 20031119
Permit Number 20031119
Review Stop E
Sequence Number 1
Notes
Date Text
2020-03-31 15:04:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) LOAD CALCULATION FOR THE ADDES LOADS PROVIDE
 ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. NEC 220
  
 2) PANEL SCHEDULE REQUIRED. PROVIDE PANEL SCHEDULE
 INDICATING ANY NEW OR ALTERED CIRCUITS 215.5
  