Plan Review Notes
Plan Review Notes For Permit 20031112
Permit Number 20031112
Review Stop G
Sequence Number 1
Notes
Date Text
2020-03-24 15:36:091. FBC 107.2.1 PROVIDE COMPLETE INSTALLATION PLAN
 DRAWING FOR CONNECTION OF GAS TO POOL WATER HEATER,
 INCLUDING GAS RISER DIAGRAM WITH LEGIBLE PRINTING,
 INCLUDING ANY OTHER EXISTING APPLIANCES AND BTUH
 VALUES, PIPE SIZING CRITERIA, WHERE EXISTING IS
 LOCATED, EXISTING PIPING ON PLAN, HOW IT IS TO BE RE
 ROUTED, PIPING MATERIALS AND VALVING. IT APPEARS A BBQ
 IS BEING REMOVED?
 2. FBC 107.2.1 POOL HEATER BROCHURE IS INADEQUATE IN
 THAT THE SIZE, MODEL OR ANY OTHER INFORMATION IS GIVEN.
 3. FBC FUEL GAS SECTION 404. PLEASE NOT THAT PIPING IN
 CONCEALED LOCATIONS SHALL NOT HAVE UNIONS, TUBING
 FITTINGS, RIGHT AND LEFT COUPLINGS, BUSHINGS,
 COMPRESSION COUPLINGS AND SWING JOINTS MADE BY
 COMBINATIONS OF FITTINGS UNLESS THE FITTINGS ARE LISTED
 FOR USE IN CONCEALED LOCATIONS.
 4. FBC 107.2.1 PROVIDE DETAILS OF POOL HEATER
 INSTALLATION INCLUDING APPROVED HURRICANE TIEDOWNS FOR
 THE HEATER.
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  