| 1ST REVIEW - FINISHED CONSTRUCTION ELEVATION |
| CERTIFICATE |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. FEMA FORM 086-0-33 ELEVATION CERTIFICATE IS OUT OF |
| DATE. SUBMIT ELEVATION CERTIFICATE ON CURRENT FORM. |
| |
| 2. STATE NUMBER OF FLOOD OPENINGS ON LINE A9 (B). |
| |
| 3. STATE NET AREA OF FLOOD OPENINGS ON LINE A9 (C). |
| |
| 4. LINE C2 (E) SHOWS ELEVATION OF EQUIPMENT SERVICING |
| THE BUILDING AT 6.92. THIS ELEVATION SHALL BE AT OR |
| ABOVE DESIGN FLOOD ELEVATION OF 8.0 FT. NAVD88. |
| |
| 5. PHOTOGRAPHS PROVIDE DO NOT COMPLY WITH THE |
| REQUIREMENTS OF LINE A6. PROVIDE PHOTOS OF FLOOD VENTS. |
| |
| 6. PROVIDE PRODUCT APPROVALS FOR FLOOD VENTS - SMART |
| VENT MODEL 1540-520. |
| |
| 7. LOCATION OF FLOOD VENTS ARE MISSING ON PLANS. SUBMIT |
| A REVISION TO PERMIT 18050588. SHOW LOCATION OF FLOOD |
| VENTS ON FOUNDATION PLAN. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |