Date |
Text |
2020-03-23 14:18:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET FP 1 - THERE IS NO INDICATION OF A FIRE |
| SPRINKLER IN THE ELEVATOR PIT. |
| |
| PER NFPA 13 |
| |
| 8.15.5 ELEVATOR HOISTWAYS AND MACHINE ROOMS. |
| 8.15.5.1* SIDEWALL SPRAY SPRINKLERS SHALL BE INSTALLED |
| AT THE BOTTOM |
| OF EACH ELEVATOR HOISTWAY NOT MORE THAN 2 FT (0.61 M) |
| ABOVE THE FLOOR OF THE PIT. |
| 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE |
| ELEVATOR |
| HOISTWAY BY 8.15.5.1 SHALL NOT BE REQUIRED FOR |
| ENCLOSED, NONCOMBUSTIBLE |
| ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBLE |
| HYDRAULIC FLUIDS. |
| |
| PLEASE PROVIDE DETAILS OR CORRECT. |
| |
| |
| |
| 2) SHEET FP 1 - THERE IS AN INDICATION AT THE ENTRY OF |
| A UTILITY ROOM UNDER THE STAIRS. |
| |
| THERE DOES NOT APPEAR TO BE A SPRINKLER HEAD PROTECTING |
| THIS AREA. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| 3) SHEET FP 1 - THERE IS AN INDICATION ON AN ENTRY |
| AREA. |
| |
| THERE DOES NOT APPEAR TO BE SPRINKLER HEAD PROTECTING |
| THIS AREA. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| 4) SHEET FP 3 - THERE IS NO INDICATION OF FIRE |
| SPRINKLER PROTECTION AT THE TOP OF HOISTWAY |
| |
| PER NFPA 13 |
| |
| 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE |
| REQUIRED IN ELEVATOR |
| MACHINE ROOMS, ELEVATOR MACHINERY SPACES, CONTROL |
| SPACES, OR |
| HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE |
| WITH THE |
| APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE |
| BUILDING |
| CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL |
| ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR |
| IS |
| DEDICATED TO ELEVATOR EQUIPMENT ONLY. |
| (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY |
| SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF |
| TRACTION |
| ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER |
| AUTOMATIC |
| FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA72. |
| (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL |
| SPACE, |
| OR HOISTWAY OF TRACTION ELEVATORS IS SEPARATED FROM THE |
| REMAINDER |
| OF THE BUILDING BY WALLS AND FLOOR/CEILING OR ROOF/ |
| CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF |
| NOT LESS |
| THAN THAT SPECIFIED BY THE APPLICABLE BUILDING CODE. |
| (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE |
| PERMITTED |
| TO BE STORED IN ELEVATOR MACHINE ROOMS, MACHINERY |
| SPACES, CONTROL ROOMS, CONTROL SPACES, OR HOISTWAYS OF |
| TRACTION |
| ELEVATORS. |
| (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC |
| TYPE. |
| 8.15.5.4* AUTOMATIC SPRINKLERS IN ELEVATOR MACHINE |
| ROOMS OR |
| AT THE TOPS OF HOISTWAYS SHALL BE OF ORDINARY- OR |
| INTERMEDIATETEMPERATURE |
| RATING. |
| 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY |
| SPRINKLERS SHALL |
| BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS. |
| 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE |
| ELEVATOR HOISTWAY |
| BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY |
| FOR PASSENGER |
| ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND |
| THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF |
| ASME |
| A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| 5) SHEET FP 3 - THERE IS AN INDICATION OF AN OUTDOOR |
| PORCH OR BALCONY WITH CEILING FANS WITH FIRE SPRINKLER |
| PROTECTION. |
| |
| 8.15.7* EXTERIOR PROJECTIONS. |
| 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3, |
| OR |
| 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER |
| EXTERIOR |
| PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. |
| 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| WHERE |
| THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS |
| THAT |
| ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE |
| RETARDANT? |
| TREATED WOOD AS DEFINED IN NFPA 703. |
| 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| FROM BELOW |
| THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION, |
| PROVIDED |
| THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS |
| ARE NONCOMBUSTIBLE, |
| LIMITED-COMBUSTIBLE, OR FIRE RETARDANT?TREATED |
| WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR |
| PROJECTIONS CONTAIN |
| ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE |
| FOLLOWING |
| UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES: |
| (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH |
| NONCOMBUSTIBLE |
| INSULATION |
| (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE |
| NONCOMBUSTIBLE |
| OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED |
| TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE |
| ENCLOSED |
| JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME, |
| INCLUDING |
| SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR |
| WITHIN |
| THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC |
| [SEE |
| 11.2.3.1.4(4)(D)] |
| (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR |
| PROJECTIONS |
| NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| 6) SHEET FP 3 - SPRINKLER HEAD LOCATION IN THE HALL |
| INDICATES SEVERAL HEADS THAT APPEAR TO BE TOO CLOSE TO |
| THE WALL. |
| |
| WITH NO DIMENSION INDICATED, PLEAE PROVIDE THE REQUIRED |
| DIMENSION FROM THE WALL TO AVOID POSSIBLE INSTALLATION |
| ERROR AND FAILED INSPECTION. |
| |
| |
| |
| |
| 7) THERE WE NO MANUFACTURES SPEC SHEETS PROVIDED TO |
| REVIEW AND VERIFY MATERILAS AND CALCULATIONS. |
| |
| PLEASE PROVIDE EQUIPMENT SPEC SHEETS. |
| |
| |
| |
| 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |