2020-04-13 14:57:24 | REVIEWED BY JERRY SMITH, RESULTS ENTERED BY JP. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20031051 3510 N FLAGLER |
| MASTER PERMIT 19080919 |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1. THIS WAS SUBMITTED AS A REVISION TO PERMIT |
| 19080919.THAT PERMIT SET INCLUDED SHEETS A-100 AND |
| ME-1. THIS REVISION IS FOR SHEETS A-201 AND A-202. |
| PROVIDE CLARIFICATION AND/OR CORRECTIONS AS NEEDED. |
| PROVIDE NARRATIVE OF REVISION. WPB FBC 107.2.1 (IT |
| APPEARS THAT NOT ALL OF THE SHEETS WERE UPLOADED. WE |
| RECEIVED A-100, ME-1, AND A 2 SHEET PLAN ENTITLED |
| PERMIT PHASE I REVISION SHEETS WHICH JUST INCLUDED |
| ANOTHER COPY OF A-100 AND ME-1. PROVIDE REVISED |
| SHEETS.) |
| 2. WITHOUT BEING ABLE TO REVIEW THE NOTED NEW SHEETS |
| A-201 AND A-202 WHICH PLAN SHEET ME-1 REFERS TO, THE |
| PLUMBING REVIEW CANNOT BE COMPLETED. THE PLUMBING RISER |
| DIAGRAM ON PLAN SHEET ME-1 APPEARS TO BE IN COMPLIANCE. |
| BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE |
| COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN |
| PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM |
| THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND |
| NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF |
| PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY |
| ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM |
| REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES |
| / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO |
| AVOID VOIDING OF THE PERMIT |
| 3. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF |
| PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON |
| RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A |
| DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY |
| VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS |
| 471/481 |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20031051 3510 N FLAGLER |
| MASTER PERMIT 19080919 |
| |
| BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE |
| |
| COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN |
| |
| PROFESSIONAL, |
| |
| CONTRACTORS OR THEIR REPRESENTATIVES FROM THE |
| |
| RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND |
| |
| NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF |
| |
| PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY |
| |
| ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM |
| |
| REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES |
| |
| / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO |
| |
| AVOID VOIDING OF THE PERMIT. |