| 20031021 360 ROSEMARY AVE |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| THE FOLLOWING REVIEW ADDRESSES ONLY REV 7 ON PLAN SHEET |
| P1.01 V2 SUBMITTED ON 3/19/2020. |
| SUBMITTED PLAN SHEET P5.03 V2 REQUIRES A MECHANICAL |
| REVIEW. |
| |
| RE: P1.01; GREASE INTERCEPTOR. PER WPB FBC 107.2.1, |
| PROVIDE SPECIFICATIONS, DETAIL FOR AND CALCULATIONS FOR |
| SIZING OF THE GREASE INTERCEPTORS. |
| A SEPARATE PERMIT IS REQUIRED FOR THE GREASE |
| INTERCEPTOR. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |