2022-01-20 14:10:28 | FAILED |
| |
| PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| |
| 1) REPEAT COMMENT: RESOLUTION 13-19, WHICH APPROVED THE |
| PROJECT INCLUDED THE REQUIREMENT THAT CERTAIN ITEMS |
| REQUIRED PRIOR TO THE SUBMITTAL OF THE BUILDING PERMIT |
| FOR SITE IMPROVEMENTS, WHICH INCLUDES THE FOUNDATION |
| PERMIT. PROVIDE EVIDENCE THAT THE FOLLOWING HAS BEEN |
| COMPLETED: |
| |
| A. ABANDON OR RELOCATE THE FPL EASEMENT ALONG THE SOUTH |
| PROPERTY LINE. THE DEVELOPER, BASED ON DISCUSSIONS WITH |
| FPL, PRESENTED A TEMPORARY POWER ROUTING PLAN TO CITY |
| STAFF; HOWEVER, THE FINAL PLAN AND FPL'S SIGN OFF ARE |
| NOT INCLUDED WITH THE RESUBMITTAL. SHEET E1.050 DOES |
| NOT SPECIFY WHEN THE EASEMENT WILL BE ABANDONED. ***** |
| EVIDENCE THAT THIS CONDITION HAS BEEN MET HAS STILL NOT |
| BEEN PROVIDED. ***** |
| |
| 2) REPEAT COMMENT: PROVIDE INFORMATION ON THE REQUIRED |
| CONDITION SURVEY: RESOLUTION 13-19 REQUIRES THAT THE |
| DEVELOPER SHALL PERFORM A CONDITION SURVEY OF THE |
| ADJOINING PROPERTIES PRIOR TO THE COMMENCEMENT OF ANY |
| CONSTRUCTION OR DEMOLITION ACTIVITIES. THE DEVELOPER |
| SHALL CONFORM TO THE APPROPRIATE INDUSTRY STANDARDS |
| APPROVED BY THE CITY'S BUILDING DIVISION IN MONITORING |
| THE VIBRATION EFFECTS ON THE ADJOINING PROPERTIES; THIS |
| MAY INCLUDE, BUT IS NOT LIMITED TO, THE PLACEMENT OF |
| SEISMIC METERS, INSPECTIONS, AND SIMILAR ACTIVITIES. |
| ***** EVIDENCE THAT THIS CONDITION HAS BEEN MET HAS |
| STILL NOT BEEN PROVIDED. ***** |
| |
| 3) REPEAT COMMENT: EV PROVISIONS - ZONING STAFF HAS |
| REVIEWED AND NEEDS CLARIFICATION NARRATIVE ON THE EV |
| PROVISION. COMMENTS BELOW MAY CHANGE BASED ON THE |
| NARRATIVE. THE NARRATIVE SHALL VERIFY THE RESOLUTION |
| NO. 13-19 EV REQUIREMENTS. |
| |
| A. IT APPEARS THAT THE GUEST SPACES ARE ONLY GETTING EV |
| LEVEL 1, INSTEAD OF THE LEVEL 2 THAT ARE REQUIRED. |
| ***** THE COMMENT RESPONSE STATES THAT ALL EV CHARGING |
| STATIONS ARE DESIGNED FOR LEVEL 2 CAPABILITIES AND THAT |
| THE ARCHITECT WILL UPDATE LABEL TO REFLECT THE REQUIRED |
| LEVEL 2 SPACE. NO NEW PLANS WERE SUBMITTED SHOWING A |
| TAG DESIGNATING LEVEL 2 GUEST SPACES TO SHOW COMPLIANCE |
| WITH THIS REQUIREMENT. THERE IS A SYMBOL ON THE KEY |
| THAT WOULD DESIGNATE LEVEL 2. THIS SYMBOL IS USED ON |
| THE BASEMENT LEVEL B2 TO DESIGNATE THE EV LEVEL 2 |
| SPACES. ***** |
| |
| 4) REPEAT COMMENT: THE FOLLOWING DIMENSIONS PROVIDED ON |
| SHEET A1.100 (SITE PLAN) DO NOT MATCH THE SAME |
| DIMENSIONS ON SHEET A1.01 (GROUND FLOOR PLAN) SUBMITTED |
| WITH THE MINOR PLANNED DEVELOPMENT AMENDMENT: |
| |
| A. WEST SETBACK DIMENSION OF 5 FEET 3 INCHES FOR THE |
| GENERATOR PIT. THE MINOR AMENDMENT PLANS SHOW A SETBACK |
| DIMENSION OF 5 FEET 6 INCHES AT THE SAME LOCATION. |
| STAFF HAS APPROVED THE MINOR PLANNED DEVELOPMENT |
| AMENDMENT, SO THIS PLAN MUST BE CORRECTED TO SHOW |
| APPROVED CONDITIONS. THIS INCORRECT SETBACK IS ALSO |
| SHOWN ON SHEET A1.1B1. |
| |
| 5) THE ABOVE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE |
| PERMITS WITH PLANS: |
| |
| A. THE WALLS, FENCES, GATES AND COLUMNS REQUIRE A |
| SEPARATE PERMIT WITH PLANS. |
| B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG |
| PARK ITEMS, BENCHES/PLAZA AREA, ETC. |
| C. LANDSCAPE |
| D. IRRIGATION |
| E. GENERATOR - PLEASE NOTE THAT THE FULL HEIGHT OF THE |
| GENERATOR DOES NOT APPEAR TO BE SCREENED AS REQUIRED BY |
| RESOLUTION NO. 13-19. HEDGES MAY NOT EXCEED 10 FEET IN |
| HEIGHT, SO YOU WILL NEED TO LOWER THE GENERATOR |
| PROFILE. |
| F. WATER FEATURES |
| G. PARKING STRIPING |
| H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE |
| ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN |
| PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET |
| OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE |
| REQUIRED WITH THE PERMITS. |
| I. BICYCLE RACKS, INCLUDES THE BICYCLE STORAGE ROOM. |
| |