Date |
Text |
2021-10-15 16:55:23 | FAILED |
| |
| PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| |
| 1) REPEAT COMMENT: RESOLUTION 13-19, WHICH APPROVED THE |
| PROJECT INCLUDED THE REQUIREMENT THAT CERTAIN ITEMS |
| REQUIRED PRIOR TO THE SUBMITTAL OF THE BUILDING PERMIT |
| FOR SITE IMPROVEMENTS, WHICH INCLUDES THE FOUNDATION |
| PERMIT. PROVIDE EVIDENCE THAT THE FOLLOWING HAS BEEN |
| COMPLETED: |
| |
| A. ABANDON OR RELOCATE THE FPL EASEMENT ALONG THE SOUTH |
| PROPERTY LINE. THE DEVELOPER, BASED ON DISCUSSIONS WITH |
| FPL, PRESENTED A TEMPORARY POWER ROUTING PLAN TO CITY |
| STAFF; HOWEVER, THE FINAL PLAN AND FPL'S SIGN OFF ARE |
| NOT INCLUDED WITH THE RESUBMITTAL. SHEET E1.050 DOES |
| NOT SPECIFY WHEN THE EASEMENT WILL BE ABANDONED. |
| |
| 2) REPEAT COMMENT: PROVIDE INFORMATION ON THE REQUIRED |
| CONDITION SURVEY: RESOLUTION 13-19 REQUIRES THAT THE |
| DEVELOPER SHALL PERFORM A CONDITION SURVEY OF THE |
| ADJOINING PROPERTIES PRIOR TO THE COMMENCEMENT OF ANY |
| CONSTRUCTION OR DEMOLITION ACTIVITIES. THE DEVELOPER |
| SHALL CONFORM TO THE APPROPRIATE INDUSTRY STANDARDS |
| APPROVED BY THE CITY'S BUILDING DIVISION IN MONITORING |
| THE VIBRATION EFFECTS ON THE ADJOINING PROPERTIES; THIS |
| MAY INCLUDE, BUT IS NOT LIMITED TO, THE PLACEMENT OF |
| SEISMIC METERS, INSPECTIONS, AND SIMILAR ACTIVITIES. |
| |
| 3) REPEAT COMMENT: EV PROVISIONS - ZONING STAFF HAS |
| REVIEWED AND NEEDS CLARIFICATION NARRATIVE ON THE EV |
| PROVISION. COMMENTS BELOW MAY CHANGE BASED ON THE |
| NARRATIVE. THE NARRATIVE SHALL VERIFY THE RESOLUTION |
| NO. 13-19 EV REQUIREMENTS. |
| |
| A. IT APPEARS THAT THE GUEST SPACES ARE ONLY GETTING EV |
| LEVEL 1, INSTEAD OF THE LEVEL 2 THAT ARE REQUIRED. |
| |
| 4) REPEAT COMMENT: THE SURVEY PREPARED BY MILLER LAND |
| SURVEYING PROVIDED WITH THE PERMIT IS NOT THE LATEST |
| SURVEY THAT WAS PROVIDED FOR THE SITE PLAN APPROVAL. |
| THE SURVEY PROVIDED BY GEOPOINT SURVEYING DOES NOT |
| MATCH WHAT WAS PRESENTED AS THE ACCURATE PROPERTY |
| BOUNDARIES SHOWN ON THE MILLER LAND SURVEYING SURVEY. |
| THE CORRECT, ACCURATE SURVEY IS REQUIRED. |
| |
| 5) THE FOLLOWING DIMENSIONS PROVIDED ON SHEET A1.100 |
| (SITE PLAN) DO NOT MATCH THE SAME DIMENSIONS ON SHEET |
| A1.01 (GROUND FLOOR PLAN) SUBMITTED WITH THE MINOR |
| PLANNED DEVELOPMENT AMENDMENT ? WEST SETBACK OF 5 FEET |
| 3 INCHES FOR THE GENERATOR PIT, NORTH SETBACK OF 20 |
| FEET 2 INCHES VIOLATES THE APPROVED SETBACK (ALSO DOES |
| NOT MATCH PERMIT SHEET A1.1B1), SOUTH B1 WALL IS |
| INCONSISTENT WITH DIMENSION ON SHEET A1.1B1. |
| ADDITIONALLY, THE DIMENSIONS TO THE COLUMNS TO THE |
| AMENITY DECK HAVE NOT BEEN PROVIDED. NOTE: CHECK ALL |
| SETBACKS FOR CONSISTENCY. PERMIT PLAN SHET A1.101 IS |
| INCONSISTENT WITH PERMIT PLANS AND THE SAME PLAN |
| SUBMITTED WITH THE MINOR AMENDMENT. |
| |
| 6) THE CIVIL PLANS UPLOADED ON MAY 7, 2021, ARE NOT THE |
| LATEST VERSION OF THE CIVIL PLANS THAT HAVE BEEN |
| SUBMITTED TO THE CITY. THE MOST CURRENT PLANS NEED TO |
| BE WITH THE PERMIT. |
| |
| 7) THE ABOVE GRADE IMPROVEMENTS REQUIRE REVIEW AS |
| SEPARATE PERMITS WITH PLANS: |
| |
| A. THE WALLS, FENCES, GATES AND COLUMNS REQUIRE A |
| SEPARATE PERMIT WITH PLANS. |
| B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG |
| PARK ITEMS, BENCHES/PLAZA AREA, ETC. |
| C. LANDSCAPE |
| D. IRRIGATION |
| E. GENERATOR - PLEASE NOTE THAT THE FULL HEIGHT OF THE |
| GENERATOR DOES NOT APPEAR TO BE SCREENED AS REQUIRED BY |
| RESOLUTION NO. 13-19. HEDGES MAY NOT EXCEED 10 FEET IN |
| HEIGHT, SO YOU WILL NEED TO LOWER THE GENERATOR |
| PROFILE. |
| F. WATER FEATURES |
| G. PARKING STRIPING |
| H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE |
| ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN |
| PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET |
| OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE |
| REQUIRED WITH THE PERMITS. |
| I. BICYCLE RACKS, INCLUDES THE BICYCLE STORAGE ROOM. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |