2020-06-18 13:26:531) SUBMIT PLUMBING FIXTURE CALCULATIONS FOR THE MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES BASED ON THE
 OCCUPANT LOADS OF THE DIFFERENT AREAS ON LEVEL 01.PER
 MY CALCULATIONS BASED ON THE OCCUPANT LOADS SHOWN ON
 SHT.LS1.101, SEPARATE FACILITIES SHALL BE REQUIRED FOR
 MALES AND FEMALES PER FBC-PLUMBING SEC.403.2.
 2) PER MY CALCULATIONS AND TABLE 403.1 OF FBC-PLUMBING,
 2 WATER CLOSETS AND 1 LAVATORY ARE REQUIRED FOR THE
 MALES AND 3 WATER CLOSETS AND 1 LAVATORY ARE REQUIRED
 FOR THE FEMALES FOR LEVEL 01.
 3) SHT. 00.200 - BUILDING TYPE TABLE - THE NOTE AT THE
 BOTTOM REFERS TO THE 2010 FBC. REVISE THE NOTE TO READ
 2017 FBC.
 4) SUBMIT FOR ALL THE UNDERSLAB PIPING (SANITARY,
 STORM, ETC.) THAT IS GOING TO BE INSTALLED UNDER THIS
 FOUNDATION PERMIT. ALSO, TAG ALL RISERS FOR
 IDENTIFICATION. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 5) SHT. P2.1B2 - TAG ALL RISERS FOR IDENTIFICATION. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT DETAILS AND CALCULATIONS FOR THE LINT
 INTERCEPTOR. THE INTERCEPTOR SHALL COMPLY WITH 2017
 FBC-PLUMBING SEC. 103.6.
 7) SHT. LS1.101 - SHOW THE SUBCATEGORY OF THE ASSEMBLY
 OCCUPANCY ON THE OCCUPANT LOAD TABLE PER FBC-BUILDING
 SEC. 303 AND TABLE 403.1 OF FBC-PLUMBING.
 NOTE: THESE PLANS WERE REVIEWED FOR THE PLUMBING FOR
 THE FOUNDATION ONLY. A REVIEW WAS NOT PERFORMED FOR
 COMPLIANCE WWITH THE FBC-ACCESSIBILITY OR THE FAIR
 HOUSING ACT GUIDELINES. COMPLIANCE WITH THESE STANDARDS
 WILL BE DONE UNDER THE FULL BUILDING SUBMITTAL REVIEW
 ALONG WITH ALL OTHER REQUIRED CODES, STANDARDS AND
 REGULATIONS.
  