2020-06-18 13:26:53 | 1) SUBMIT PLUMBING FIXTURE CALCULATIONS FOR THE MINIMUM |
| NUMBER OF REQUIRED PLUMBING FIXTURES BASED ON THE |
| OCCUPANT LOADS OF THE DIFFERENT AREAS ON LEVEL 01.PER |
| MY CALCULATIONS BASED ON THE OCCUPANT LOADS SHOWN ON |
| SHT.LS1.101, SEPARATE FACILITIES SHALL BE REQUIRED FOR |
| MALES AND FEMALES PER FBC-PLUMBING SEC.403.2. |
| 2) PER MY CALCULATIONS AND TABLE 403.1 OF FBC-PLUMBING, |
| 2 WATER CLOSETS AND 1 LAVATORY ARE REQUIRED FOR THE |
| MALES AND 3 WATER CLOSETS AND 1 LAVATORY ARE REQUIRED |
| FOR THE FEMALES FOR LEVEL 01. |
| 3) SHT. 00.200 - BUILDING TYPE TABLE - THE NOTE AT THE |
| BOTTOM REFERS TO THE 2010 FBC. REVISE THE NOTE TO READ |
| 2017 FBC. |
| 4) SUBMIT FOR ALL THE UNDERSLAB PIPING (SANITARY, |
| STORM, ETC.) THAT IS GOING TO BE INSTALLED UNDER THIS |
| FOUNDATION PERMIT. ALSO, TAG ALL RISERS FOR |
| IDENTIFICATION. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 5) SHT. P2.1B2 - TAG ALL RISERS FOR IDENTIFICATION. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 6) SUBMIT DETAILS AND CALCULATIONS FOR THE LINT |
| INTERCEPTOR. THE INTERCEPTOR SHALL COMPLY WITH 2017 |
| FBC-PLUMBING SEC. 103.6. |
| 7) SHT. LS1.101 - SHOW THE SUBCATEGORY OF THE ASSEMBLY |
| OCCUPANCY ON THE OCCUPANT LOAD TABLE PER FBC-BUILDING |
| SEC. 303 AND TABLE 403.1 OF FBC-PLUMBING. |
| NOTE: THESE PLANS WERE REVIEWED FOR THE PLUMBING FOR |
| THE FOUNDATION ONLY. A REVIEW WAS NOT PERFORMED FOR |
| COMPLIANCE WWITH THE FBC-ACCESSIBILITY OR THE FAIR |
| HOUSING ACT GUIDELINES. COMPLIANCE WITH THESE STANDARDS |
| WILL BE DONE UNDER THE FULL BUILDING SUBMITTAL REVIEW |
| ALONG WITH ALL OTHER REQUIRED CODES, STANDARDS AND |
| REGULATIONS. |
| |