2020-03-24 14:15:23 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20030979
  
 CODES IN EFFECT:
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE BUILDING REVIEWERS COMMENTS.
  
 2) PLEASE PROVIDE ENERGY REPORT FOR THE PROPOSED
 CONDITIONED SPACE. SEE FBC EC 101.5.1.1.2
  
 3) PROVIDE MANUAL J,S AND D CALCULATIONS FOR THE
 PROPOSED NEW SPLIT SYSTEM. SEE FBC RES M1401.3; FBC EC
 RE403.7.1
  
 4) OUTDOOR CONDENSING UNIT MUST BE TIED DOWN PER
 MANUFACTURE INSTALLATION INSTRUCTIONS OR THE DESIGN
 MUST BE STAMPED BY AND ENGINEER. SEE FBC RES M1307.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  