| 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20030979 |
| |
| CODES IN EFFECT: |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SEE BUILDING REVIEWERS COMMENTS. |
| |
| 2) PLEASE PROVIDE ENERGY REPORT FOR THE PROPOSED |
| CONDITIONED SPACE. SEE FBC EC 101.5.1.1.2 |
| |
| 3) PROVIDE MANUAL J,S AND D CALCULATIONS FOR THE |
| PROPOSED NEW SPLIT SYSTEM. SEE FBC RES M1401.3; FBC EC |
| RE403.7.1 |
| |
| 4) OUTDOOR CONDENSING UNIT MUST BE TIED DOWN PER |
| MANUFACTURE INSTALLATION INSTRUCTIONS OR THE DESIGN |
| MUST BE STAMPED BY AND ENGINEER. SEE FBC RES M1307.2 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |