Plan Review Notes
Plan Review Notes For Permit 20030946
Permit Number 20030946
Review Stop HIST
Sequence Number 3
Notes
Date Text
2020-07-23 13:21:26THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. THE SITE PLANS PROVIDED DOES NOT ACCURATELY REFLECT
 THE BUILDING. STAFF BELIEVES THE ORIENTATION MAY BE
 MIXED UP.
 2. NO MULLION INFORMATION WAS PROVIDED FOR THE PAIRED
 OR TRIPLE WINDOWS. PROVIDE MULLION INFORMATION.
 3. PROVIDE PHOTOS OF EACH ELEVATION WITH OPENING LABELS
 MATCHING THE WINDOW SCHEDULE AND SITE PLAN. IF NOT
 POSSIBLE FOR EACH ELEVATION, PROVIDE MORE THAN ONE
 PHOTO.
 4. THE FIRST-FLOOR TRIPLE WINDOWS NEED TO HAVE MULLIONS
 SIZED TO WHAT WAS EXISTING BEFORE THE WINDOWS WERE
 REPLACED.
 5. THE SECOND-FLOOR TRIPLE WINDOWS NEED TO HAVE A
 MULLIONS SIZED TO WHAT WAS EXISTING BEFORE THE WINDOWS
 WERE REPLACED.
 6. THE WINDOW LOCATED ABOVE THE BALCONY WILL NEED TO BE
 REMOVED. A PAIRED FRENCH DOOR WITH 10-LITE EACH WILL
 NEED TO BE INSTALLED.
 7. ALL WINDOWS WILL NEED TO HAVE WINDOW TRIM AND SILL
 RECONSTRUCTED IN WOOD.
 8. ALL WINDOWS REQUIRING A MULLION SHALL HAVE A MULLION
 TO MATCH THE EXISTING/ORIGINAL MULLION WIDTH. THIS WAS
 LIKELY BETWEEN 4 AND 6 INCHES.
 9. BASED ON PREVIOUS CONVERSATIONS, ALL WINDOWS WERE
 BEING REPLACED. ARE ANY WINDOWS NOT BEING REPLACED?
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE:
 1. ALL WINDOWS NEED TO BE SIZED TO FIT THE ORIGINAL
 WINDOW FRAME OPENING. ALL WINDOWS SHALL MATCH THE
 INSET/LOCATION/DEPTH OF THE ORIGINAL WINDOWS WITHIN THE
 FRAME OPENING.
 2. ALL MULLIONS NEED TO BE SIZED TO THE WIDTH OF THE
 ORIGINAL MULLION WITHIN THE WINDOW FRAME OPENING. ALL
 MULLIONS NEED TO MATCH THE LOCATION/PLACEMENT OF THE
 ORIGINAL MULLION WITHIN THE FRAME OPENING.
 3. ALL NEW STREET-FACING WINDOWS NEED TO HAVE CLEAR
 GLASS ONLY.
 4. THE SMALL 8-LITE WINDOWS ON EITHER SIDE OF THE FRONT
 DOOR SHALL REMAIN AND BE REPAIRED AS NEEDED.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771