2020-03-19 19:22:39 | 03/19/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 2. PLEASE PROVIDE A DETAIL OF HOW SHOWER PAN IS GOING |
| TO BE INSTALLED, IT MUST HAVE A SLOPED MORTAR BED THAT |
| IS PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF |
| 1/4" IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM |
| CORNER, BACKING AROUND THE PERIMETER AND BEFORE FINAL |
| MORTAR APPLICATION PLACE SOME PEA GRAVEL OVER WEEP |
| HOLES SO THE MORTAR DOES NOT COVER THEM PER |
| MANUFACTURES SPECIFICATIONS AND PER THE 2017 FBC |
| SECTION R 2709.2 LINING REQUIRED. |
| |
| 3. INDIVIDUAL SHOWER AND TUB/ SHOWER COMBINATION VALVES |
| SHALL BE EQUIPPED WITH CONTROL VALVES OF THE |
| PRESSURE-BALANCE, THERMOSTATIC-MIXING OR COMBINATION |
| PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A |
| HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME |
| A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET |
| TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN 120 |
| F (49 C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE USED |
| FOR COMPLIANCE WITH THIS SECTION PER THE 2017 FBC |
| SECTION R 2708.4, SHOWER CONTROL VALVES. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |