2020-08-04 16:37:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1
  
 RISER DOES NOT SHOW MAIN DISCONNECT AS STATED IN THE
 NOTES
  
 400A FUSES CAN NOT PROTECT 3/0 AND 1/0 CONDUCTORS UNDER
 THESE CONDITIONS, FEEDING SUB PANELS MUST BE TAPS?
 240.21 WHICH ONE 10' 25' RULE?
  
 CONDUCTORS TO FPL COPPER OR ALUMINUMU?
  
 VALUE OF PERMIT HAS NOT BEEN ADJUSTED.