2020-05-19 15:06:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE HAS BEEN A SUBSTANTIAL AMOUNT OF WORK ADDED TO
 THE PLANS AND YET THE REVISION FORM INDICATES THAT
 THERE IS NO INCREASE IN THE VALUE OF WORK PERFORMED.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS FOR
 TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC 109.3
 2. WIRE SPECIFIED IN RISER DIAGRAM FOR FEEL TO FPL IS
 NOT SIZED CORRECTLY. FOR A 3 PHASE SERVICE THERE SHOULD
 BE A MINIMUM OF 4 WIRES. ADDITIONALLY, THE WIRE MUST BE
 SIZED FOR THE MAIN OVERCURRENT PROTECTION, WHICH IS
 SHOWN AS 400 AMP. PROVIDE CORRECTION. NEC 250.24(C),
 310.15(B)(16)
 3. RISER DIAGRAM SHOWS FIVE 1/0 CONDUCTORS IN A 2 INCH
 CONDUIT TO FEED PANEL C. THIS CONDUIT IS UNDERSIZED.
 PROVIDE CORRECTION. NEC INFORMATIVE ANNEX C
 4. LOAD CALCULATION SHOWN DOES NOT MATCH THE LOADS
 SHOWN IN PANEL SCHEDULES. PROVIDE ACCURATE LOAD
 CALCULATION INCLUDING ALL LOADS. LOAD FOR PANEL C IS
 NOT REFLECTED ACROSS ALL PHASES. PROVIDE CORRECTION.
 NEC 220
 5. SHEET E-2 SPECIFIES THE 2011 NEC AS BASIS FOR
 DESIGN. THIS IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. FBC PREFACE, ALSO SEE ABOVE.
 6. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  