2020-05-19 15:06:46 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THERE HAS BEEN A SUBSTANTIAL AMOUNT OF WORK ADDED TO |
| THE PLANS AND YET THE REVISION FORM INDICATES THAT |
| THERE IS NO INCREASE IN THE VALUE OF WORK PERFORMED. |
| PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF |
| WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS FOR |
| TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC 109.3 |
| 2. WIRE SPECIFIED IN RISER DIAGRAM FOR FEEL TO FPL IS |
| NOT SIZED CORRECTLY. FOR A 3 PHASE SERVICE THERE SHOULD |
| BE A MINIMUM OF 4 WIRES. ADDITIONALLY, THE WIRE MUST BE |
| SIZED FOR THE MAIN OVERCURRENT PROTECTION, WHICH IS |
| SHOWN AS 400 AMP. PROVIDE CORRECTION. NEC 250.24(C), |
| 310.15(B)(16) |
| 3. RISER DIAGRAM SHOWS FIVE 1/0 CONDUCTORS IN A 2 INCH |
| CONDUIT TO FEED PANEL C. THIS CONDUIT IS UNDERSIZED. |
| PROVIDE CORRECTION. NEC INFORMATIVE ANNEX C |
| 4. LOAD CALCULATION SHOWN DOES NOT MATCH THE LOADS |
| SHOWN IN PANEL SCHEDULES. PROVIDE ACCURATE LOAD |
| CALCULATION INCLUDING ALL LOADS. LOAD FOR PANEL C IS |
| NOT REFLECTED ACROSS ALL PHASES. PROVIDE CORRECTION. |
| NEC 220 |
| 5. SHEET E-2 SPECIFIES THE 2011 NEC AS BASIS FOR |
| DESIGN. THIS IS NOT THE CURRENT CODE. PROVIDE |
| CORRECTION. FBC PREFACE, ALSO SEE ABOVE. |
| 6. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND |
| PANELS. NEC 110.3, 110.9 |
| 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |