Plan Review Notes For Permit 20030898 |
Permit Number |
20030898 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-05-18 16:10:42 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | FBC A FIGURE 404.2.4.1, ON SHEET A-1 (LIFE SAFETY), | | ALONG EXIT PATH "A" THE INTERIOR DOOR DOES NOT MEET THE | | (18") MANEUVERING CLEARANCE REQUIREMENTS OF ACCESSIBLE | | ROUTES. | | | | |
|