Plan Review Notes
Plan Review Notes For Permit 20030898
Permit Number 20030898
Review Stop M
Sequence Number 1
Notes
Date Text
2020-03-23 09:05:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020898
 3/23/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1 & M-2: THERE IS NO JUSTIFICATION FOR THE
 ADDED 2.5 TON AC SYSTEM IN THE TENANT SPACE. THERE
 APPEARS TO BE NO INCREASE IN SQUARE FOOTAGE OR HEAT
 LOAD FOR THE SPACE. PLEASE NOTE THAT REVISED AC AND
 ENERGY CALCULATIONS ARE REQUIRED- SECTIONS C403.2.1,
 C101.5, & C401.2 FBC EC
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  