Plan Review Notes For Permit 20030898 |
Permit Number |
20030898 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-03-23 09:05:24 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #20020898 | | 3/23/20 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M-1 & M-2: THERE IS NO JUSTIFICATION FOR THE | | ADDED 2.5 TON AC SYSTEM IN THE TENANT SPACE. THERE | | APPEARS TO BE NO INCREASE IN SQUARE FOOTAGE OR HEAT | | LOAD FOR THE SPACE. PLEASE NOTE THAT REVISED AC AND | | ENERGY CALCULATIONS ARE REQUIRED- SECTIONS C403.2.1, | | C101.5, & C401.2 FBC EC | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|