Plan Review Notes
Plan Review Notes For Permit 20030885
Permit Number 20030885
Review Stop E
Sequence Number 1
Notes
Date Text
2020-03-25 08:40:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE
 RESPONSIBLE PERSON THAT DOES THE DESIGN. THIS
 RESPONSIBLE PERSON SHOULD BE EITHER A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED (AND
 SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  