Plan Review Notes
Plan Review Notes For Permit 20030880
Permit Number 20030880
Review Stop M
Sequence Number 1
Notes
Date Text
2020-03-26 16:04:39MR. PAINE SENT A LETTER CLARIFYING THE SCOPE OF WORK IN
 THIS SUNROOM. IT WAS AN EXISTING CONDITIONED SUNROOM
 THAT THEY ARE ADDING A LAUNDRY ROOM AND BATHROOM IN.
 THIS WILL NEED A MECHANICAL PERMIT.
2020-03-24 13:17:161ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20030880
  
 CODES IN EFFECT:
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE ENERGY CALCULATION FOR THE ENCLOSED
 ROOM. SEE: FBC FS 107.2.1
  
 2) HOW ARE YOU GOING TO CONDITION THIS NEWLY ENCLOSED
 ROOM? FBC EC 101.5.1.1.2 SIMULATED PERFORMANCE
 ALTERNATIVE. AN ACCURATELY COMPLETED RESIDENTIAL
 BUILDING FORM R405 (GENERATED BY COMMISSION APPROVED
 SOFTWARE) SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 TO DEMONSTRATE CODE COMPLIANCE BY SECTION 405.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  