2020-03-26 16:04:39 | MR. PAINE SENT A LETTER CLARIFYING THE SCOPE OF WORK IN |
| THIS SUNROOM. IT WAS AN EXISTING CONDITIONED SUNROOM |
| THAT THEY ARE ADDING A LAUNDRY ROOM AND BATHROOM IN. |
| THIS WILL NEED A MECHANICAL PERMIT. |
2020-03-24 13:17:16 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20030880 |
| |
| CODES IN EFFECT: |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE ENERGY CALCULATION FOR THE ENCLOSED |
| ROOM. SEE: FBC FS 107.2.1 |
| |
| 2) HOW ARE YOU GOING TO CONDITION THIS NEWLY ENCLOSED |
| ROOM? FBC EC 101.5.1.1.2 SIMULATED PERFORMANCE |
| ALTERNATIVE. AN ACCURATELY COMPLETED RESIDENTIAL |
| BUILDING FORM R405 (GENERATED BY COMMISSION APPROVED |
| SOFTWARE) SHALL BE SUBMITTED TO THE BUILDING OFFICIAL |
| TO DEMONSTRATE CODE COMPLIANCE BY SECTION 405. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |