2020-03-26 17:58:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY BN, BU, PX |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) VALUE IS LOW FOR THIS SIZE SYSTEM. (SYSTEM THIS SIZE |
| IS $26,000) |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 2) SHOW HOW PLAN MEETS THE REQUIREMENTS OF 705.12 |
| |
| 705.12 (D)(2)(3) (B) WHERE TWO SOURCES, ONE A UTILITY |
| AND THE OTHER AN INVERTER, ARE LOCATED AT OPPOSITE ENDS |
| OF A BUSBAR THAT CONTAINS LOADS, THE SUM OF 125 PERCENT |
| OF THE INVERTER(S) OUTPUT CIRCUIT CURRENT AND THE |
| RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR |
| SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE |
| BUSBAR. THE BUSBAR SHALL BE SIZED FOR THE LOADS |
| CONNECTED IN ACCORDANCE WITH ARTICLE 220 |