Plan Review Notes
Plan Review Notes For Permit 20030875
Permit Number 20030875
Review Stop E
Sequence Number 1
Notes
Date Text
2020-03-26 17:58:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE IS LOW FOR THIS SIZE SYSTEM. (SYSTEM THIS SIZE
 IS $26,000)
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SHOW HOW PLAN MEETS THE REQUIREMENTS OF 705.12
  
 705.12 (D)(2)(3) (B) WHERE TWO SOURCES, ONE A UTILITY
 AND THE OTHER AN INVERTER, ARE LOCATED AT OPPOSITE ENDS
 OF A BUSBAR THAT CONTAINS LOADS, THE SUM OF 125 PERCENT
 OF THE INVERTER(S) OUTPUT CIRCUIT CURRENT AND THE
 RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR
 SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE
 BUSBAR. THE BUSBAR SHALL BE SIZED FOR THE LOADS
 CONNECTED IN ACCORDANCE WITH ARTICLE 220