Plan Review Notes
Plan Review Notes For Permit 20030857
Permit Number 20030857
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-13 15:42:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20030857 1551 N FLAGLER DR # 1014
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, IDENTIFY ON THE PLAN LAYOUT
 WHERE THE TUB AND SHOWER VALVE IS GOING TO BE REPLACED
 WITH THE SHOWER.
 2. PER FBC PL 417.4.1, BATHTUB FLOORS, SHOWER FLOORS,
 WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE INSTALLED
 SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS SHALL BE
 CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET ABOVE THE
 ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES ABOVE THE
 DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A
 WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE
 TUB OR SHOWER FLOOR.
 3. PER WPB FBC 107.2.1, SHOW TYPE OF MATERIAL OF SHOWER
 DRAIN PIPE. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR TO BE USED FOR DEALING
 WITH THE SHOWER FLOOR PENETRATION AND THE ELIMINATED
 TUB DRAIN OPENING AS REQUIRED BY FBC 714.4.1 THROUGH
 714.4.4.1.2.
 4. PER WPB FBC 107.2.1, PROVIDE SHOWER LINER MATERIAL
 TYPE.
 5. PER FBC PL 424.3, INDIVIDUAL SHOWER AND TUB-SHOWER
 COMBINATION VALVES SHALL BE BALANCED-PRESSURE,
 THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
 6. THE PERMIT APPLICATION INCLUDES NEW CABINETS, SHOWER
 ENCLOSURES, VANITIES AND TILE, BUT A-1 FLOOR PLAN NOTES
 ONLY ELECTRICAL (NOT NOTED ON APPLICATION) AND
 REPLACEMENT OF A TUB WITH A SHOWER WITH A SHOWER CURB
 DETAIL. CLARIFY AND PROVIDE COMPLETE SCOPE.
 7. PER FBC PL 604.9, THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER. A WATER-HAMMER ARRESTOR
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED (AT THE DISHWASHER AND ICE LINE TO
 REFRIGERATOR). WATER-HAMMER ARRESTORS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. WATER-HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010.
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20030857 1551 N FLAGLER DR # 1014
  
  