2020-08-13 15:42:11 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20030857 1551 N FLAGLER DR # 1014 |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1. PER WPB FBC 107.2.1, IDENTIFY ON THE PLAN LAYOUT |
| WHERE THE TUB AND SHOWER VALVE IS GOING TO BE REPLACED |
| WITH THE SHOWER. |
| 2. PER FBC PL 417.4.1, BATHTUB FLOORS, SHOWER FLOORS, |
| WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE INSTALLED |
| SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS SHALL BE |
| CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL |
| EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET ABOVE THE |
| ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES ABOVE THE |
| DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A |
| WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE |
| TUB OR SHOWER FLOOR. |
| 3. PER WPB FBC 107.2.1, SHOW TYPE OF MATERIAL OF SHOWER |
| DRAIN PIPE. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE |
| RATING OF NOT LESS THAN 1 HOUR TO BE USED FOR DEALING |
| WITH THE SHOWER FLOOR PENETRATION AND THE ELIMINATED |
| TUB DRAIN OPENING AS REQUIRED BY FBC 714.4.1 THROUGH |
| 714.4.4.1.2. |
| 4. PER WPB FBC 107.2.1, PROVIDE SHOWER LINER MATERIAL |
| TYPE. |
| 5. PER FBC PL 424.3, INDIVIDUAL SHOWER AND TUB-SHOWER |
| COMBINATION VALVES SHALL BE BALANCED-PRESSURE, |
| THERMOSTATIC OR COMBINATION |
| BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER |
| COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE |
| EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF |
| THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD |
| ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| UTILIZED FOR COMPLIANCE WITH THIS SECTION. |
| 6. THE PERMIT APPLICATION INCLUDES NEW CABINETS, SHOWER |
| ENCLOSURES, VANITIES AND TILE, BUT A-1 FLOOR PLAN NOTES |
| ONLY ELECTRICAL (NOT NOTED ON APPLICATION) AND |
| REPLACEMENT OF A TUB WITH A SHOWER WITH A SHOWER CURB |
| DETAIL. CLARIFY AND PROVIDE COMPLETE SCOPE. |
| 7. PER FBC PL 604.9, THE FLOW VELOCITY OF THE WATER |
| DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE |
| POSSIBILITY OF WATER HAMMER. A WATER-HAMMER ARRESTOR |
| SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE |
| UTILIZED (AT THE DISHWASHER AND ICE LINE TO |
| REFRIGERATOR). WATER-HAMMER ARRESTORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTRUCTIONS. WATER-HAMMER ARRESTORS SHALL CONFORM TO |
| ASSE 1010. |
| |
| END OF COMMENTS. |
| |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| FROM THE FIRST REVIEW. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20030857 1551 N FLAGLER DR # 1014 |
| |
| |